7ML19985GE04
SITRANS LC500 – OPERATING INSTRUCTIONS
Page 63
Appendix A
Analog Output Signalling (proportional or 2-state): menu level 0
Analog mode (the loop-current) can provide either:
•
a 4 to 20 / 20 to 4 mA output proportional to the percent of the range
or
•
a 4 or 20 / 20 or 4 mA output, when 2-state mode is selected
Upper Threshold Delay (2-state mode)
The Upper Threshold Setting controls the Activation delay: the amount of time that has to
pass uninterrupted with the probe covered to a level above the Upper Threshold Setting
before the timer expires. When the timer expires, the output signal complies with the
setting from Menu 08 for a covered probe. Whenever the level drops below the Upper
Threshold Setting before the timer expires, the timer is restarted.
As an extra identifier, an upward running A is displayed to the right of the value.
1. Set the loop-current control (Menu 07) to 2-state mode.
2. Set the rotary switch to 3.
3. Press the RED (+) or BLUE(–) button to increase or decrease the value.
or: Press and hold a button to start a repeat function.
or: Press and hold both buttons simultaneously to toggle the value between
minimum (0) and maximum (100).
Lower Threshold Delay (2-state mode)
The Lower Threshold Setting controls the Deactivation delay: the amount of time that has
to pass uninterrupted with the probe covered to a level below the Lower Threshold
Setting before the timer expires. When the timer expires, the output signal will comply
with the setting from Menu 08 for an uncovered probe. Whenever the level rises above
the Lower Threshold Setting before the timer expires, the timer is restarted.
As an extra identifier, a downward running A is displayed to the right of the value.
Note:
To set values for Upper and Lower Threshold Delay, and Upper and Lower
Threshold Setting (2-state mode), the loop-current menu (07) must be in 2-state mode.
When the loop-current control is in analog mode, the LCD displays only - - - - for
these menu selections.