Page 64
SITRANS LC500 – OPERATING INSTRUCTIONS
7ML19985GE04
Appendix A
1. Set the loop-current control (Menu 07) to 2-state mode.
2. Set the rotary switch to 4.
3. Press the RED (+) or BLUE(–) buttons to increase or decrease the value.
or: Press and hold a button to start a repeat function.
or: Press and hold both buttons simultaneously to toggle the value between
minimum (0) and maximum (100).
Upper Threshold Setting (2-state mode)
The Upper Threshold Setting is the % of range above which the probe is considered
covered. In order to switch the output signal, the corresponding delay time has to be met
(Menu 03).
The loop-current control (Menu 07) must be in 2-state mode for this menu to display the
Upper Threshold Setting in percent. As an extra identifier, an upward ramp
is
displayed to the right of the value.
1. Set the loop-current control (Menu 07) to 2-state mode.
2. Set the rotary switch to 5.
3. Press the RED (+) or BLUE (–) button to increase or decrease the value.
or: Press and hold a button to start a repeat function.
Menu
Item
Affected
by:
Rotary
Switch
Position
Left
Arrow
Mode
Added
Indicator
Description Values
04
07
4
Off
2-
state
Downward
running A at
right of value
Lower
Threshold
Delay
in
seconds
Ana-
log
*
Display
shows
- - - -
Menu
Item
Affected
by:
Rotary
Switch
Position
Left
Arrow
Mode
Added
Indicator
Description Values
05
07
5
Off
2-state
Upward
ramp at right
of value
Upper
Threshold
Setting
% of
range
Analog *
Display
shows
- - - -