Page 72
SITRANS LC500 – OPERATING INSTRUCTIONS
7ML19985GE04
Appendix A
Digital Fault Signalling
Controls the solid-state switch response to a fault/failure and allows you to select either
contact open or contact closed. With contact closed the solid-state switch will be on:
with contact open the solid-state switch will be off.
While a button is pressed, the LCD displays F: cc
1
(contact closed) or F: co (contact open).
When the button is released an equal sign (=) indicating status replaces the colon, and
the reading depends on the status of the probe.
Example: F = cc is selected (contact closed when fault is detected)
•
If a fault condition exists when the button is released, the display changes from
F: cc to F = cc.
•
If no fault condition exists when the button is released, the display shows F: cc.
•
If you press either button briefly, the LCD displays the current setting, in this
case, F: cc.
Set the rotary switch to 8. Press the RED (+) or BLUE (–) button to change the setting. The
disabled mode can be restored at any time by pressing both buttons simultaneously for
more than one second.
Note:
This signal has precedence over the settings on Menu 17.
1.
A colon at the extreme left of the display appears while the button is pressed to
indicate when a setting is accepted, for example : S: cc.
Menu
Item
Rotary
Switch
Position
Left
Arrow
Mode
Description Action
Values
18
8
On
Disabled
*
Press and hold
both buttons
Display
shows
F: - -
Digital
Signalling
Mode
Contact Closed:
switch on
Press and hold
RED (+) button
Display
shows
F: cc
Contact Open:
switch off
Press and hold
BLUE (–) button
Display
shows
F: co