SITRANS LU180
Operating Instructions, 06/2016, A5E37100674-AA
27
Operating
6
6.1
Adjustments
There are several operating adjustments that can be made to the SITRANS LU180.
To access the operating adjustments, simultaneously press the "4" and "20" keys until the
desired adjustment is obtained. A viewing sequence of the stored value is automatically initiated.
During this time the value can be changed by pressing either the "4" or "20" key. After viewing or
changing, operation automatically reverts to the Run mode (6 secs).
Adjustment
Display
4 mA calibration (Page 28), scrolling
20 mA calibration (Page 29), scrolling
Blanking (Page 29)
Speed of response (Page 30)
Fail-safe (Page 32)
Fail-safe timer (Page 33)
Units (Page 33)
Note
Calibration bypasses the measurement response rate.
Summary of Contents for Sitrans LU-180