Operating
6.11 Fail-safe timer
SITRANS LU180
Operating Instructions, 06/2016, A5E37100674-AA
33
6.11
Fail-safe timer
The fail-safe timer allows the user to vary the ‘waiting’ period from the time a loss of echo or
operating fault condition begins, until the fail-safe default is effected. The ‘waiting’ period is
adjustable from 1 to 15 minutes, in 1 minute increments.
The fail-safe timer value will default to settings determined by the Speed of response (Page 30).
If a different value is desired, the fail-safe timer should be adjusted
after the speed of response
is set.
6.12
Adjusting the fail-safe timer
To change the fail-safe setting, go to the 'FSt'' display (as described in Adjustments (Page 27)),
and proceed as follows:
1.
Press the "20" key to increase the 'waiting' period, and press the "4" key to decrease it.
2.
Once you have reached the appropriate value, stop pressing the key. The display
automatically returns to the Run mode (6 secs).
6.13
Units
The units of the measurement reading can be selected as follows:
1 = metres, m (factory setting)
2 = feet, ft
The selected units are also applicable to the 'Blanking' adjustment.
Summary of Contents for Sitrans LU-180
Page 1: ...Operating Instructions LU 180 Sitrans LU 180 Edition 06 2016 Ultrasonic Transmitters ...
Page 7: ...Introduction SITRANS LU180 6 Operating Instructions 06 2016 A5E37100674 AA ...
Page 9: ...Description SITRANS LU180 8 Operating Instructions 06 2016 A5E37100674 AA ...
Page 37: ...Troubleshooting SITRANS LU180 36 Operating Instructions 06 2016 A5E37100674 AA ...
Page 41: ...Technical data 8 7 Approvals SITRANS LU180 40 Operating Instructions 06 2016 A5E37100674 AA ...