6.4
20 mA calibration
20 mA calibration initiated
view stored 20 mA calibration value
(i.e. 0.50 m)
press ”4” to increase to new calibration value
(i.e. 0.45 m)
new calibration value
6.5
Blanking
Blanking is used to ignore the zone in front of the transducer where false echoes are at a level
that interfere with the processing of the true echo. It is measured outward from the sensor face.
The minimum recommended blanking value is 0.25 m (0.82 ft) but can be increased in order to
extend the blanking.
①
SITRANS LU150
②
Blanking