SITRANS P220 (7MF1567)
14
A5E03304437-AA, 09/2017
7.4
Return procedure
Enclose the bill of lading, return document and decontamination certificate in a clear plastic pouch and attach it firmly to the
outside of the packaging.
Required forms
●
Delivery note
●
Return document (
http://www.siemens.com/processinstrumentation/returngoodsnote
with the following information:
–
Product (item description)
–
Number of returned devices/replacement parts
–
Reason for returning the item(s)
●
Decontamination declaration (
http://www.siemens.com/sc/declarationofdecontamination
With this declaration you warrant "that the device/replacement part has been carefully cleaned and is free of residues.
The device/replacement part does not pose a hazard for humans and the environment."
If the returned device/replacement part has come into contact with poisonous, corrosive, flammable or water-
contaminating substances, you must thoroughly clean and decontaminate the device/replacement part before returning it
in order to ensure that all hollow areas are free from hazardous substances. Check the item after it has been cleaned.
Any devices/replacement parts returned without a decontamination declaration will be cleaned at your expense before
further processing.
7.5
Disposal
Devices described in this manual should be recycled. They may not be disposed of in the municipal
waste disposal services according to the Directive 2012/19/EC on waste electronic and electrical
equipment (WEEE).
Devices can be returned to the supplier within the EC, or to a locally approved disposal service for
eco-friendly recycling. Observe the specific regulations valid in your country.
Further information about devices containing batteries can be found at: Information on
battery/product return (WEEE) (
https://support.industry.siemens.com/cs/document/109479891/
Note
Special disposal required
The device includes components that require special disposal.
•
Dispose of the device properly and environmentally through a local waste disposal contractor.
8
Technical specifications
Mode of operation
Measuring range
≥
2.5 ...
≤
600 bar
Piezo-resistive with stainless steel diaphragm
Input
Measured variable input
Measuring range for relative pressure
Overload limit
Burst pressure
0 ... 2.5 bar g
≥
-0.8 /
≤
6.25 bar g
25 bar g
0 ... 4 bar g
≥
-0.8 /
≤
10 bar g
40 bar g
0 ... 6 bar g
≥
-1 /
≤
15 bar g
36 bar g
0 ... 10 bar g
≥
-1 /
≤
25 bar g
60 bar g
0 ... 16 bar g
≥
-1 /
≤
40 bar g
96 bar g