Configuration
6.2 Configuring the busbar run layout
SIVACON 8PS - Configuring with LX system
120
Configuration Manual, 10/2011, A5E02194899-02
6.2.4
Configuring example
This configuring example refers to the planning example from the SIVACON 8PS Planning
Manual, Chap. 7. Please refer to this planning manual for details of the planning procedure.
System selection
The system size LXA0551 results from the planning example in the planning manual.
After selection of the correct system, the following documents must be prepared for ordering:
●
Installation plan busbar plan
●
Parts list busbar plan
●
Binding order
Explanations
The rated current is the same for the mounting positions horizontal, edgewise and vertical.
The standard degree of protection is IP54. The storey height is 3.40 m.
Since this is a single system, one fixing bracket per storey must be mounted for vertical
installation.
At the start of the run, you must configure an expansion compensation mechanism to be
fixed at the lower end. (For more information see Configuring vertical busbar runs
(Page 119))
In practice, the configured run layout frequently differs to the originally planned run layout.