Configuration
6.2 Configuring the busbar run layout
SIVACON 8PS - Configuring with LX system
Configuration Manual, 10/2011, A5E02194899-02
123
6.2.5
Special cases
6.2.5.1
Functional endurance
Please refer to the SIVACON 8PS Planning Manual for details of standards, application
areas and planning.
Overview of implementing the functional endurance channel and reduction factors
System
Functional
endurance
class
Density d
[mm]/PROMATEC
T plate type
Outside dimensions
1)
of
the Promat channel
(W [mm] x H [mm])
Reduction factor
2)
according to
functional endurance class and
mounting position
Horizontal
Vertical
Edgewise
3)
Flat
E60
30 / LS
250 x 250
0.7
0.7
0.7
LX.01, LX.02
E120
50 / LS
290 x 290
0.6
0.6
0.6
E60
30 / LS
250 x 280
0.7
0.7
0.7
LXC03, LX.04
E120
50 / LS
290 x 320
0.6
0.6
0.6
E60
30 / LS
250 x 320
0.7
0.7
0.7
LX.05
E120
50 / LS
290 x 360
0.6
0.6
0.6
E60
30 / LS
250 x 400
0.7
0.7
0.7
LX.06, LX.07
E120
50 / LS
290 x 440
0.6
0.6
0.6
E90
30 / LS
250 x 550
0.7
0.7
0.7
LX.08
E120
50 / LS
270 x 570
0.65
0.65
0.65
E90
30 / LS
250 x 710
0.7
0.7
0.7
LX.09, LX.10
E120
50 / LS
270 x 730
0.65
0.65
0.65
1)
Outside dimensions are valid for versions with 4 barriers. Dimensions for versions with
3 and 2 barriers are available on request.
2)
The reduction factors are based on the rated current I
e
and an ambient temperature of
35°C (24-hour average). In the event of temperature deviations, reduction factors
should be adjusted accordingly.
3)
Mounting position horizontal edgewise:
LXA/LXC (trunking conductor)
Use of LXC at 6300 A
For requirements with rated currents of 6300 A, it is necessary to use two single systems
LXC07 (I
e
= 3200 A) in parallel. In the installation manual "Installation with LX System"
(order number: A5E01120816) you will find solution suggestions on how to use external
copper material to implement an electrical connection for parallel switching on the infeeds
such as non-Siemens distribution boards or transformer connections.
Please contact the relevant product manager for more detailed information about
dimensioning and current carrying capacity.