7.16 Fire load for trunking units without tap-off points
SIVACON 8PS - Configuring with LX system
154
Configuration Manual, 10/2011, A5E02194899-02
7.16
Fire load for trunking units without tap-off points
System
Fire load [kWh/m]
LXA(C)0141
LXA(C)0151
1.95
LXA(C)0241
LXA(C)0251
2.04
LXC0341
LXC0351
2.42
LXA(C)0441
LXA(C)0451
2.53
LXA0541
LXA0551
3.54
LXC0541
LXC0551
3.48
LXA(C)0641
LXA(C)0651
5.33
LXA(C)0741
LXA(C)0751
5.42
LXA(C)0841
LXA(C)0851
7.28
LXA(C)0941
LXA(C)0951
10.88
LXA1041
LXA1051
11.07
For trunking units with tap-off points, regardless of system size, a fire load of 2.9 kWh must
be taken into account for each tap-off point.
Fire load values for LX...30, LX...52, LX...53, LX...54, LX...61, LX...62 are only available on
request.