Dimension drawings
8.3 Feeder units
SIVACON 8PS - Configuring with LX system
Configuration Manual, 10/2011, A5E02194899-02
165
8.3.1.2
Universal busbar connection unit AS3
//
,
D
3(11
E
E
S
Q
S
3(
K
K
Figure 8-13 LX .....-AS3(+LX-.A)/(+LX-.C)
//
,
D
3(11
E
E
S
Q
S
3(
K
K
1)
Reference dimension for configuring = centre of joint block to centre of 1st connection tag.
More detailed information: See Chapter Feeder units (Page 164).
2)
Total length l of the connection unit is the sum of the configured connection tag distances.
Figure 8-14 LX .....-AS3(+LX-.B)/(+LX-.D)
System
a
b1
b2
h1
h2
p min.
p max. n min.
n max.
LXA(C)01
255
140
140
137
96.5
405
750
150
400
LXA(C)02
255
140
140
137
96.5
405
750
150
400
LXA(C)03
255
140
140
162
96.5
405
750
150
400
LXA(C)04
255
140
140
162
96.5
405
750
150
400
LXA(C)05
255
140
140
207
96.5
405
750
150
400
LXA(C)06
255
140
140
287
96.5
405
750
155
400
LXA(C)07
255
140
140
287
96.5
405
750
155
400
LXA(C)08
315
200
200
439
96.5
405
750
275
400
LXA(C)09
315
200
200
599
96.5
405
750
275
400
LXA(C)10
315
200
200
599
96.5
405
750
275
400