3.3 Application areas of the individual SIVACON 8PS systems
SIVACON 8PS - Configuring with LX system
Configuration Manual, 10/2011, A5E02194899-02
19
3.3
Application areas of the individual SIVACON 8PS systems
Application areas of the individual SIVACON 8PS systems
The individual systems of SIVACON 8PS are designed for the building and industry
application areas. They enable flexible power distribution in building construction and a safe
power supply to electronic loads.
The following table contains information on the application areas:
System
Location of
Use
Application areas
LX
LD
LR
Banks
Insurance companies
For power distribution in multi-storey buildings with a
mainly vertical busbar run layout.
X
-
-
To avoid neutral conductor overloading due to electronic
loads subject to harmonics
X
-
-
To prevent interference potentials in the rail enclosure
from negatively influencing operability of loads
X
-
-
If there is a high density of load tap-off points in the
smallest of spaces
X
-
-
Internet providers
Computer centres
Broadcasting stations
If structural conditions permit only a vertical busbar run
layout for power distribution
X
-
-
To protect loads against negative influences of magnetic
field emissions
-
X
-
Public
buildings
Shopping centres
Furniture stores
Trade fairs
Airports
Hospitals
Clinics
Office buildings
For power distribution with a mainly horizontal busbar
run layout and IP34 degree of protection
-
X
-
When plug-in tap-off points for loads up to 1250 A are
required
-
X
-
When load tap-off points have to have a high short-
circuit resistance, e.g.
I
CC
= 100 kA / I
cf
= 120 kA
-
X
-
When plug-in tap-off points for loads up to 630 A are
sufficient
X
-
-
When the IP34 degree of protection is sufficient.
-
X
-
When the IP54 degree of protection is sufficient
X
-
-
Industrial buildings
Production environments
When the degree of protection IP6x is required.
-
-
X
For power conveyance under extreme production
conditions
-
-
X
For power conveyance outside closed buildings
-
-
X
Industrial
buildings
Industrial production with
extreme conditions
When a horizontal busbar run layout and the IP68
degree of protection are required
-
-
X