Product selection
4.3 Selection tables
SIVACON 8PS - Configuring with LX system
Configuration Manual, 10/2011, A5E02194899-02
63
4.3.4.2
Tap-off units with fuse switch disconnector up to 630 A
Equipment features
●
Can be connected under load
1)
●
Tap-off via tap-off point
●
Degree of protection IP54, increased to IP55 with installation kit
●
Tap-off units LX-AK5/FSH...
–
Can only be connected on systems LX...3., LX...4. and LX...5.
●
Tap-off units LX-AK6/FSH...
–
Connection device for insulated PE conductor
–
Can only be connected on systems LX...6.
●
Cable connection
–
Single conductor cable connection
2)
only for tap-off units from 400 A
3)
–
Multi-core cable connection for the systems LX...52, LX...54 and LX...62 maximum
connection cross-section only to 100% neutral conductor
●
Cable entry
–
Front: Tap-off units up to 250 A
–
Side and front: Tap-off units from 315 A to 630 A
1)
Please observe national regulations. Connection under load may not be permissible.
2)
Aluminium plate undrilled, cable glands provided by the customer, see Technical data
3)
For 125 A to 250 A on request