Scale parameters and functions
8.13 DR 13 RS485 parameters
SIWAREX WP231
Manual, 07/2014, A5E31238908A-02
103
Variable
Note
Type
Length
(bytes)
Rw
Default
Min.
Max.
Modbus
registers
Bit 10
Reserve
BIT
0
rw
0
0
1
1564.6
Bit 11
Reserve
BIT
0
rw
0
0
1
1564.5
Bit 12
Reserve
BIT
0
rw
0
0
1
1564.4
Bit 13
Reserve
BIT
0
rw
0
0
1
1564.3
Bit 14
Reserve
BIT
0
rw
0
0
1
1564.2
Bit 15
Reserve
BIT
2
rw
0
0
1
1564.1
(Page 105)
MODBUS address for Vito mod-
ule
USHORT
2
rw
20
1
255
1565
(Page 105)
Decimal place for Siebert display SHORT
2
rw
0
-
-
1566
MODBUS
RTU frame
delay
Delay time for response with
MODBUS RTU in ms (RS485)
USHORT
2
rw
0
-
-
1567
Reserve 3
Reserve
FLOAT
4
rw
0
-
-
1568
8.13.2
RS485 protocol
This parameter defines the protocol for communication via the RS485 interface.
Value
Protocol
0
No communication/protocol
1
Modbus RTU
2
SIEBERT display
8.13.3
RS485 baud rate
This parameter defines the baud rate for the RS485 interface.
Value
Baud rate
0
1 200 bps
1
2 400 bps
2
9 600 bps
3
19 200 bps
4
38 400 bps
5
57 600 bps
6
115 000 bps
Summary of Contents for SIWAREX WP231
Page 16: ...Safety notes 2 1 General safety instructions SIWAREX WP231 16 Manual 07 2014 A5E31238908A 02 ...
Page 132: ......
Page 174: ...Technical data 13 3 Approvals SIWAREX WP231 174 Manual 07 2014 A5E31238908A 02 ...
Page 180: ...List of abbreviations SIWAREX WP231 180 Manual 07 2014 A5E31238908A 02 ...
Page 182: ...Index SIWAREX WP231 182 Manual 07 2014 A5E31238908A 02 ...