Technical data
13.1 Technical specifications
SIWAREX WP231
Manual, 07/2014, A5E31238908A-02
165
Analog output
The set replacement value is output in case of a fault or SIMATIC CPU stop.
Table 13- 4 Technical specifications:
Error limit according to DIN 1319-1 of full-scale value at
20 °C +10 K
0 ... 20 mA:
≤
0.5 %
4 mA to 20 mA: ≤
0.3 %
Refresh rate
≤
100 ms
Resolution
14 bit
Measuring ranges
0 mA to 20 mA
4 mA to 20 mA
Max. output current
24 mA
Error signal (if configured (FW))
22 mA
Max. load
600
Ω
Temperature coefficient range
≤
± 25 ppm/K v. E.
Temperature coefficient zero point
typ. ± 0.3
μA/K
Linearity error
≤
0.05 %
Electrical isolation
500 V AC
Cable length
max. 100 m, twisted and shielded
Figure 13-1 Current ranges for signal level to Namur recommendation NE43
Digital outputs (DQ)
The set value is output at the digital output in case of a fault or SIMATIC CPU stop.
A freewheeling diode has to be installed at the consumer with inductive loads at the digital
output.
Table 13- 5 Technical specifications: Digital outputs
Quantity
4 (high-side switch)
Supply voltage range
19.2 V DC to 28.8 V DC
Max. output current per output
0.5 A (ohmic load)
Max. total current for all outputs
2.0 A
Refresh rate (FW)
100
Switching delay
typ. 25 µs turn on
typ. 150 µs turn off
RDSON
< 0.25 Ω
Short-circuit proof
Yes
Electrical isolation
500 V AC
Cable length (meter)
Max. 500 m shielded, 150 m unshielded
Summary of Contents for SIWAREX WP231
Page 16: ...Safety notes 2 1 General safety instructions SIWAREX WP231 16 Manual 07 2014 A5E31238908A 02 ...
Page 132: ......
Page 174: ...Technical data 13 3 Approvals SIWAREX WP231 174 Manual 07 2014 A5E31238908A 02 ...
Page 180: ...List of abbreviations SIWAREX WP231 180 Manual 07 2014 A5E31238908A 02 ...
Page 182: ...Index SIWAREX WP231 182 Manual 07 2014 A5E31238908A 02 ...