Technical data
13.1 Technical specifications
SIWAREX WP231
166
Manual, 07/2014, A5E31238908A-02
Digital inputs (DI)
Table 13- 6 Technical specifications: Digital inputs
Number of inputs
4
Rated voltage
24 V DC
Supply voltage range
max. 30 V DC
Power consumption at 24 V DC
4 mA
Voltage surge
35 V DC for 0.5 s
Logical signal level 1 (min)
15 V DC at 2.5 mA
Logical signal level 0 (max)
5 V DC at 1.0 mA
Sampling rate (FW)
10 ms
Filtering
0.2, 0.4, 0.8, 1.6, 3.2, 6.4 and 12.8 ms
Electrical isolation
500 V DC
Real-time clock
Table 13- 7 Technical specifications: Real-time clock
Accuracy at 25 °C
± 60 s/month
Buffered period
typ. 10 days at 25 °C
min. 6 days at 40 °C
RS485 interface
Table 13- 8 Technical specifications: RS485 interface
Standard
EIA-485
Baud rate
up to 115 kbps*
Data bits
7 or 8
Parity
even | odd | none
Stop bits
1 or 2
Terminating resistors (can be activated)
390
Ω / 220
Ω / 390
Ω
Electrical isolation
500 V AC
Transfer protocol
ASCII for remote display from Siebert and Modbus
RTU)
Cable length
≤
115 kbps max. 1 000 m
(fieldbus cable 2-wire, shielded, e.g. 6XV1830-0EH10)
Summary of Contents for SIWAREX WP231
Page 16: ...Safety notes 2 1 General safety instructions SIWAREX WP231 16 Manual 07 2014 A5E31238908A 02 ...
Page 132: ......
Page 174: ...Technical data 13 3 Approvals SIWAREX WP231 174 Manual 07 2014 A5E31238908A 02 ...
Page 180: ...List of abbreviations SIWAREX WP231 180 Manual 07 2014 A5E31238908A 02 ...
Page 182: ...Index SIWAREX WP231 182 Manual 07 2014 A5E31238908A 02 ...