Commissioning
7.7 Service with the SIWATOOL program
SIWAREX WP231
Manual, 07/2014, A5E31238908A-02
57
7.7.3.1
Entering a known SIWAREX IP address
To establish a connection to a SIWAREX module, enter the IP address in SIWATOOL.
Under the menu item "Communication", select "Set Ethernet Configuration...". Enter the IP
address of the SIWAREX module in the following window. To activate the IP address and
establish a connection to the SIWAREX module, subsequently click on "Online".
7.7.3.2
Determining an unknown IP address
If the IP address of a connected SIWAREX module is unknown, it can be determined using
the program "Primary Setup Tool". The program is included in the configuration package
(Page 175).
Install the program "Primary Setup Tool". When started, the program can determine the
Siemens devices present in the network.
The MAC (Media Access Control) address can be read on the front of the SIWAREX
module. Every device has an MAC address which is unique worldwide.
The IP address can be determined from the identified MAC address. The Primary Setup Tool
also allows the IP address of a SIWAREX module to be set/changed.
Additional information on the Primary Setup Tool can be found in the associated manual.
7.7.3.3
Setting up a network
Several SIWAREX modules can be connected together in a network via a switch. Via the
network, you can use SIWATOOL to assign parameters to and start the various modules or
connect a common Operator Panel.
7.7.4
Online parameter assignment
To switch to online mode, connect the PC to the SIWAREX module using an Ethernet cable.
Set the IP address of the SIWAREX module in the communication menu.
You can change all parameters in the SIWAREX module in online mode. The message
window shows the current contents of the message buffer of the SIWAREX module. The
current process values are displayed in the "Online" column.
For test purposes, you can send various commands to the SIWAREX module. Differences
between the online/offline data are marked in red by SIWATOOL. This affects both the
associated data record and the individual parameter.
In order to archive data, all data can be exported from the SIWAREX module and saved as a
file or printed.
Summary of Contents for SIWAREX WP231
Page 16: ...Safety notes 2 1 General safety instructions SIWAREX WP231 16 Manual 07 2014 A5E31238908A 02 ...
Page 132: ......
Page 174: ...Technical data 13 3 Approvals SIWAREX WP231 174 Manual 07 2014 A5E31238908A 02 ...
Page 180: ...List of abbreviations SIWAREX WP231 180 Manual 07 2014 A5E31238908A 02 ...
Page 182: ...Index SIWAREX WP231 182 Manual 07 2014 A5E31238908A 02 ...