Scale parameters and functions
8.7 DR 6 limit value settings
SIWAREX WP231
86
Manual, 07/2014, A5E31238908A-02
8.7.1
Limit value 1 ON, limit value 2 ON, limit value 1 OFF, limit value 2 OFF
The switch-on and switch-off points can be specified separately for each limit value as a
percentage of the measuring range. This allows both minimum and maximum value violation
monitoring with hysteresis. A delay time for switch-on and switch-off can also be specified.
Either the current net weight or the current gross weight can be selected as the reference
value for limits 1 and 2.
Maximum value monitoring is implemented with the following specifications:
●
Switch-on value > switch-off value
Minimum value monitoring is implemented with the following specification:
●
Switch-on value < switch-off value
The diagram below illustrates the function of limit values 1 and 2.
Figure 8-5
Limit value configuration
8.7.2
Delay time for limit value 1 ON, delay time for limit value 2 ON
If the weight reaches the specified switch value, a delay time (defined in ms) is launched.
Once the delay time is over, the limit switch changes status provided the weight still reaches
the specified switch value.
8.7.3
Delay time for limit value 1 OFF, delay time for limit value 2 OFF
If the weight reaches the specified switch value, a delay time (defined in ms) is launched.
Once the delay time is over, the limit switch changes status provided the weight still reaches
the specified switch value.
Summary of Contents for SIWAREX WP231
Page 16: ...Safety notes 2 1 General safety instructions SIWAREX WP231 16 Manual 07 2014 A5E31238908A 02 ...
Page 132: ......
Page 174: ...Technical data 13 3 Approvals SIWAREX WP231 174 Manual 07 2014 A5E31238908A 02 ...
Page 180: ...List of abbreviations SIWAREX WP231 180 Manual 07 2014 A5E31238908A 02 ...
Page 182: ...Index SIWAREX WP231 182 Manual 07 2014 A5E31238908A 02 ...