Scale parameters and functions
8.8 DR 7 interface parameters
SIWAREX WP231
Manual, 07/2014, A5E31238908A-02
93
8.8.6
Analog output range
This parameter is used to define the output current range.
Value
Output current
0
0 … 20 mA
1
4 … 20 mA
8.8.7
Analog output source
The analog output can be used for a range of purposes. This parameter defines the tag that
controls the analog output.
Value
Basis for the analog output
0
Gross / net value
1
Gross value
2
Net value
3
External specification, DR 17
(Specified in mA)
4
Via SIMATIC S7 I/O modules
8.8.8
Response of analog output to faults or SIMATIC STOP
This parameter defines the response of the analog output following a fault of the SIWAREX
module or SIMATIC STOP.
Value
Response
0
Switch off
1
Continue
2
Output configured output value, e.g. 3.5 mA
3
Output maximum value (24 mA, NAMUR)
8.8.9
Start value for the analog output
This parameter defines the specified value at which 0 or 4 mA is output. The value can be
greater or less than the end value.
8.8.10
End value for the analog output
This parameter defines the specified value at which 20 mA is output. The value can be
greater or less than the start value.
Summary of Contents for SIWAREX WP231
Page 16: ...Safety notes 2 1 General safety instructions SIWAREX WP231 16 Manual 07 2014 A5E31238908A 02 ...
Page 132: ......
Page 174: ...Technical data 13 3 Approvals SIWAREX WP231 174 Manual 07 2014 A5E31238908A 02 ...
Page 180: ...List of abbreviations SIWAREX WP231 180 Manual 07 2014 A5E31238908A 02 ...
Page 182: ...Index SIWAREX WP231 182 Manual 07 2014 A5E31238908A 02 ...