Scale parameters and functions
8.15 DR 15 tare settings
SIWAREX WP231
Manual, 07/2014, A5E31238908A-02
107
8.15
DR 15 tare settings
8.15.1
Overview
Data record DR 15 is used for the external specification of up to 3 tare weights.
Procedure
●
Enter the tare weight(s)
●
Transfer the data record to the scales
●
Enable a tare weight with a command
Table 8- 16 Assignment of data record 15
Variable
Note
Type
Length
(bytes)
Rw
Default
Min.
Max.
Modbus
registers
Data record
number
Contains no.
of data rec-
ord
USHORT
2
r
15
-
-
1578
Length
Data record
length infor-
mation
USHORT
2
r
28
-
-
1579
Application
Information
about which
application
the DR
belongs to
USHORT
2
r
101
-
-
1580
Version
identifier
Information
on current
data record
version
USHORT
2
r
1
1
65635
1581
(Page 108)
Tare setting
memory 1
FLOAT
4
rw
0
0
Depends on
specification
in DR 3
1582
Tare setting
memory 2
FLOAT
4
rw
0
0
Depends on
specification
in DR 3
1584
Tare setting
memory 3
FLOAT
4
rw
0
0
Depends on
specification
in DR 3
1586
Reserve 1
Reserve
SHORT
2
rw
0
0
-
1588
Reserve 2
Reserve
USHORT
2
rw
0
0
-
1589
Reserve 3
Reserve
FLOAT
4
rw
0
0
-
1590
8.15.2
Specification of tare weight 1, 2, 3
Up to three tare weights can be entered. If a tare weight is to be applied, it must be enabled
with the corresponding command. The tare weights may not exceed the maximum values
specified in data record DR 3.
Summary of Contents for SIWAREX WP231
Page 16: ...Safety notes 2 1 General safety instructions SIWAREX WP231 16 Manual 07 2014 A5E31238908A 02 ...
Page 132: ......
Page 174: ...Technical data 13 3 Approvals SIWAREX WP231 174 Manual 07 2014 A5E31238908A 02 ...
Page 180: ...List of abbreviations SIWAREX WP231 180 Manual 07 2014 A5E31238908A 02 ...
Page 182: ...Index SIWAREX WP231 182 Manual 07 2014 A5E31238908A 02 ...