background image

Document No. 997-1002 
Installation Instructions 
February 12, 2009

 

 

Page 4 of 8 

SLX Series

 

 

Figure 8: Current Input – 2-Wire Transducer. 

 

Connect the current input according to the following figure if 
a 3-wire, 4-20mA transducer is being used. 

 

Figure 9: Current Input – 3-Wire Transducer. 

 

Connect the current input according to the following figure if 
the transducer is powered by its own power source. 

 

Figure 10: Current Input – Transducer with its Own 

Power Source. 

 

Wiring Voltage Inputs 

Voltage inputs have a range of 0 to 10VDC. Connect the 
voltage input according to the following figure if a 3-wire 0-
10V transducer is being used. 

 

Figure 11: Voltage Input – 3-Wire Transducer. 

 

Connect the voltage input according to the following figure if 
the transducer is powered by its own power source. 

 

Figure 12: Voltage Input – Transducer with its Own 

Power Source. 

 

 

On the SLX-ASC-PFCU-A and SLX-P-PTU-A, the 
onboard 24VAC output with a DC power supply can 
be used to supply the current loop, as shown in 
Figure 9. It can also be used to supply the voltage, 
as shown in Figure 11

.

 Refer to the transducer 

installation guide for further details. 

 

9. SLX-RTS/SLX-STAT 

Wiring 

Each controller is compatible with the SLX-RTS line of 
standard room sensors. Refer to the SLX-RTS and SLX-STAT 
installation instructions for wiring details. 

 

10. Output Wiring 

The SLX-ASC-PFCU and SLX-P-PTU controllers have 
physical connections for four (4) relay contact outputs and four 
(4) triac outputs. In addition to these outputs, the SLX-ASC-
PFCU-A and SLX-P-PTU-A controllers have two (2) universal 
outputs. All of these outputs are software configurable. 

 

Before connecting any input equipment to the 
controller, refer to the installation guide of the 
equipment manufacturer. 

 

Wiring Relay Contact Outputs 

Three (3) relay contact outputs (DO1-DO3) can switch 3A 
(inductive/resistive) for fan speed control up to 277VAC, and 
one (1) relay contact output (DO4) can switch 3A (inductive) 
and 10A (resistive) for heater control up to 277VAC. 

 

 

Relay contact output cables must remain 
between 18 and 14AWG. Select the proper 
gauge according to the current load. 

 

All digital relay contact outputs on PFCU and 
PTU controllers are normally open. 

 

There is no voltage present on the digital output 
terminals, so an external power supply should 
be used if necessary. 

 

It is recommended to use a 4A fast-acting, high-
breaking fuse to protect the relay contact outputs 
(DO1-3) and a 15A fast-acting, high-breaking 
fuse to protect the relay contact output (DO4) 
against short circuiting when high voltage is 
being used.

 

 

Figure 13: Relay Contact Output – Fan and Reheat 

Powered by External 85-265VAC Power Supply. 

 

Wiring Triac Outputs 

The four (4) triac outputs can switch 1A at 20.4-265VAC and 
can be used to turn equipment and devices on and off (two-
state outputs) and to control valve and damper actuators 
using stroke time or Pulse Width Modulation (PWM).  

 

 

Triac output cables should be between 20 and 
18AWG. They must be at least 18AWG if they 
are switching high voltage. 

 

To measure the state of a triac output, an 
external load must be connected. 

 

When high voltage is used, you must use a 4A 
fast-acting, high-breaking fuse to protect the 
triac outputs against short circuiting. 

 

It is not necessary to use a fuse when the 
onboard 24VAC output is being used with the 
triac outputs since it already has built-in short 
circuit protection. 

 

The triac outputs work in pairs (DO5-DO6 and 
DO7-DO8) and cannot work with two different 
voltages. For example, the DO5-DO6 switch 
high voltage (85-265VAC) and DO7-DO8 switch 
the onboard 24VAC.

 

Summary of Contents for SLX-ASC-PFCU

Page 1: ...illers and boilers Moreover they are suitable for any lighting control and power measurement applications All of the controllers are based on the LONWORKS technology for peer to peer communication between controllers and are LONMARK certified Unless otherwise indicated the term PFCU is used in this document to represent both the SLX ASC PFCU and SLX ASC PFCU A models Likewise PTU represents both t...

Page 2: ...electrical shock or burn Warning Symbol Significant information required Refer to Hardware Installation Guide Double Insulation Symbol These controllers are built with double insulation 4 General Wiring Recommendations Due to HIGH VOLTAGE direct contact will cause electrical shock or burn Turn off power before any kind of servicing It is recommended to use a 2 line main power disconnect to be loca...

Page 3: ...h less than 75 23m either a shielded or unshielded 18AWG wire may be used For a wire length between 75 and 200 23 to 61m a shielded 18AWG wire is recommended The wire should be shielded on the controller side and the shield length should be kept as short as possible Wiring Digital Inputs This input configuration is used to monitor digital dry contacts as well as pulsed contacts PTU controllers onl...

Page 4: ... to the installation guide of the equipment manufacturer Wiring Relay Contact Outputs Three 3 relay contact outputs DO1 DO3 can switch 3A inductive resistive for fan speed control up to 277VAC and one 1 relay contact output DO4 can switch 3A inductive and 10A resistive for heater control up to 277VAC Relay contact output cables must remain between 18 and 14AWG Select the proper gauge according to ...

Page 5: ... 10VDC Universal Output Analog Actuator 11 Communications Wiring The recommended cable type for LON communications is 22AWG 0 65 mm twisted pair unshielded The LON communication wire is polarity insensitive and can be laid out in a bus star loop or free topology For loop topology polarity is important and special care must be taken when connecting the LON network to avoid a short circuit It is rec...

Page 6: ... jumper 6 Reconnect the power The service LED will blink twice and become solid indicating that the controller is application less The proper APB using the Commission or Load option in LNS e g SLX Series LMT can now be loaded into the controller 13 Maintenance Due to HIGH VOLTAGE direct contact will cause electrical shock or burn Turn off power before any kind of servicing The PFCU and PTU control...

Page 7: ...Page 7 of 8 15 Typical Fan Coil Application Wiring Diagram 4A Fast acting high breaking 5 x 20mm Fuse PART 216 004XP Littelfuse Fuse holder PART 3004100 Phoenix Contact 15A Fast acting high breaking 6 x 32mm Fuse PART 314015P Littelfuse Fuse holder PART 3004171 Phoenix Contact ...

Page 8: ...etwork termination Check the termination s Incorrect or broken termination s will make the communication integrity dependent upon a controller s position on the network Extra capacitance Make sure that no extra capacitance is being connected to the network other than the standard FTT circuit and a maximum of a 3 meter stub in bus topology Number of controllers on network segment exceeded The numbe...

Reviews: