7PG2113/4/5/6 Solkor Settings
©2010 Siemens Protection Devices Limited Chapter 2 Page 18 of 21
Laptop computer
RS232 to RS485
Converter with
Auto Device
Enable (ADE)
RS232 straight
through cable or
USB to RS232
Converter cable
USB or 9 pin male
D connector
9/25 pin connector
14
18
RS485 Screened
twisted pair
Rear terminals
A
B
2.1.2
Rear RS485 connection
Figure 2.1-2 RS485 connection to PC
Figure 2.1-2 RS485 connection to PC
2.1.3
Configuring Relay Data Communication
2.1.3
Configuring Relay Data Communication
Using the keys on the relay fascia scroll down the settings menus into the ‘communications’ menu and if
necessary change the settings for the communication port you are using on the relay. Reydisp software uses
IEC60870-5-103 protocol to communicate.
Using the keys on the relay fascia scroll down the settings menus into the ‘communications’ menu and if
necessary change the settings for the communication port you are using on the relay. Reydisp software uses
IEC60870-5-103 protocol to communicate.
When connecting the relay to a pc using the front USB port, the Reydisp setting software will automatically detect
the relay without making any setting changes in the relay first as long as the USB is selected to IEC60870-5-103.
When connecting the relay to a pc using the front USB port, the Reydisp setting software will automatically detect
the relay without making any setting changes in the relay first as long as the USB is selected to IEC60870-5-103.
COM1-RS485 Port
COM1-RS485 Port
COM2-USB Port
COM2-USB Port
Setting name
Setting name
Range
Default
Units
Notes
Station Address
0 … 65534 (DNP3)
1 … 254 (103)
0 … 247 (MODBUS)
0
Address given to relay to
identify that relay from
others which may be using
the same path for
communication as other
relays for example in a fibre
optic hub
DNP3 Unsolicited
Events
Disabled/Enabled Disabled
DNP3 Destination
Address
0 … 65534
0
This setting is only visible
when DNP3 Unsolicited
Events is Enabled.
COM1-RS485 Protocol
OFF, IEC60870-5-103,
MODBUS-RTU,DNP3
IEC60870-5-
103
COM1 is the rear mounted
RS485 port
COM1-RS485 Baud
Rate
75 110 150 300 600 1200
2400 4800 9600 19200
38400
19200
COM1-RS485 Parity
NONE, ODD, EVEN
EVEN
COM2-USB Protocol
OFF, IEC60870-5-103,
MODBUS-RTU,
ASCII,DNP3
IEC60870-5-
103