7PG2113/4/5/6 Performance Specification
©2010 Siemens Protection Devices Limited
Chapter 3 Page 34 of 42
2.13.6 Operate and Reset Time (59NIT)
Attribute
Value
t
basic
Starter operate time
65 ms,
±
20ms
3V
o
Applied Current (for Operate-Time)
DTL
10 x Vs
char = IDMTL
[ ]
1
M
t
Vs
0
V
3
op
−
=
,
±
5 % or
±
65 ms
t
op
Operate
time
char = DTL
t
d
,
±
1 % or
±
40ms
char = IDMTL
t
res
,
±
5 % or
±
65ms
Reset
Time
char = DTL
t
res
,
±
1 % or
±
40ms
Repeatability
±
1 % or
±
20ms
Overshoot time
< 40 ms
Disengaging time
< 100 ms