7PG2113/4/5/6 Performance Specification
©2010 Siemens Protection Devices Limited
Chapter 3 Page 35 of 42
2.14 64H Restricted Earth Fault Protection
2.14.1 Reference
Parameter
Value
Is
Setting
0.05, 0.055.… 0.95 x
In
t
d
Delay setting
0.00, 0.01…20.00, 20.10… 100, 101… 1000, 1010…
10000, 10100… 14400 s
2.14.2 Operate and Reset Level
Attribute
Value
I
op
Operate level
100 %
Is
,
±
5 % or
±
1%
xIn
Reset level
95 %
I
op
,
±
5 % or
±
0.1%
xIn
Repeatability
±
1 %
Transient overreach
(X/R
≤
100)
≤
-5 %
-10 °C to +55 °C
≤
5 %
Variation
f
nom
- 3 Hz to
f
nom
+ 2 Hz
≤
5 %
2.14.3 Operate and Reset Time
Attribute
Value
0 to 2 x
Is
, 45 ms,
±
10ms
t
basic
Element basic operate time
0 to 5 xI
s
, 35 ms,
±
10ms
t
op
Operate time following delay
t
basic
+
t
d
,
±
1% or
±
10ms
Repeatability
±
1% or
±
10ms
Overshoot time
< 40 ms
Disengaging time
< 50 ms