7PG2113/4/5/6 Performance Specification
©2010 Siemens Protection Devices Limited
Chapter 3 Page 39 of 42
3.2
50BF Circuit Breaker Fail
3.2.1 Reference
Parameter
Value
Is
Setting
0.050, 0.055… 2.0 x
In
I4
Setting
0.050, 0.055… 2.0 x
In
t
CBF1
Stage 1 Delay setting
20, 25… 60000ms
t
CBF2
Stage 2 Delay setting
20, 25… 60000ms
3.2.2 Operate and Reset Level
Attribute
Value
I
op
Operate level
100 %
Is
,
±
5 % or
±
1%
In
I
reset
Reset level
<
100 %
I
op
,
±
5 % or
±
1%
In
Repeatability
±
1 %
-10 °C to +55 °C
≤
5 %
Variation
f
nom
- 3 Hz to
f
nom
+ 2 Hz
≤
5 %
3.2.3 Operate and Reset Time
Attribute
Value
Stage 1
t
CBF1
,
±
1 % or
±
20ms
t
op
Stage 2
t
CBF2
,
±
1 % or
±
20ms
Repeatability
±
1 % or
±
20ms
Overshoot
< 2 x 20ms
Disengaging time