23/26
Building Technologies Division
CC1N7817en
24.02.2015
Connection diagrams and connection terminals
(cont’d)
3 position version with 2 end switches and 4 auxiliary switches
xx
xx
X3
X2
X1
1
2 3
V
IV
III
5
M
II
I
VI
2
1
3
4
1
2
3
4
5
6
8
78
17
d1
7/
10
13
Mains voltage terminals
Dimensioning
X1-1
Move to position (III)
Input
AC 120 V / AC 230 V
max. 1 A, cos
>0.9
X1-2
Auxiliary switch AUX (IV)
NO contact
Output
AC 120 V / AC 230 V
max. 1 A, cos
>0.9
X1-3
Auxiliary switch AUX (IV)
Input
AC 120 V / AC 230 V
max. 1 A, cos
>0.9
X1-4
Neutral
Input
AC 120 V / AC 230 V
max. 1 A, cos
>0.9
inductive
X1-5
Closing (II)
Input
AC 120 V / AC 230 V
max. 1 A, cos
>0.9
X1-6
Opening (I)
Input
AC 120 V / AC 230 V
max. 1 A, cos
>0.9
X2-1
Auxiliary switch AUX (V)
Input
AC 120 V / AC 230 V
max. 1 A, cos
>0.9
X2-2
Auxiliary switch AUX (V)
NO contact
Input
AC 120 V / AC 230 V
max. 1 A, cos
>0.9
X2-3
Position reached (I / II / III)
Output
AC 120 V / AC 230 V
max. 0.3 A, cos
>0.8
X2-4
Auxiliary switch AUX (IV)
NC opener
Output
AC 120 V / AC 230 V
max. 1 A, cos
>0.9
X2-5
Auxiliary switch AUX (V)
NC opener
Output
AC 120 V / AC 230 V
max. 1 A, cos
>0.9
X3-1
Auxiliary switch AUX (VI)
NO contact
Output
AC 120 V / AC 230 V
max. 1 A, cos
>0.9 **
X3-2
Auxiliary switch AUX (VI)
NC opener
Output
AC 120 V / AC 230 V
max. 1 A, cos
>0.9 **
X3-3
Auxiliary switch AUX (VI)
Input
AC 120 V / AC 230 V
max. 1 A, cos
>0.9 **
Notice!
** When connecting a fuel valve:
Max. 0.3 A, cos
φ
>0.8 inductive.
See SQM4x.x4xxxx in this chapter.
SQM4x.x8xxxx
Range adjustment