To ensure 

degree of protection IP 54,

 suitable Pg glands must be fitted in the actua-

tor’s Pg11 openings.
The Pg glands used must feature cable strain relief.
To ensure degree of protection IP 54 during the actuator’s entire service life, the bear-
ing of the drive shaft must be located such that it will not be directly exposed to water or
dust.

SQM4...

Mounting plate SQM4...

Secure coupling piece to drive shaft
such that intermediate plastic
piece has an axial play of about
0.2 to 0.5 mm

Mounting plate VKF41...

Spacer

VKF41...

78

14

z0

2e

/0

502

ASK33.4

Installation notes

·

 

Installation work must be carried out by qualified staff

·

 

Always run the high-voltage ignition cables separate from the unit and other cables
while observing the greatest possible distance

·

 

To ensure protection against electric shock hazard, make certain that the AC 230 V
section of the SQM4... is strictly segregated from the functional low-voltage section

·

 

The holding torque is reduced when the actuator’s power supply is switched off

The housing cover may only be removed for short periods of time for wiring or when
making the addressing. It must be made certain that dust or dirt will not get inside the
actuator while such work is carried out.

The actuator contains a printed circuit board with ESD-sensitive components.
The top side of the board carries a cover which affords protection against direct con-
tact. This protective cover may 

not

 be removed! The underside side of the board may

not be touched.

Addressing (assignment of functions) defines whether the SQM4... shall operate as a

·

 fuel 

actuator

·

 air 

damper 

actuator, 

or

·

 auxiliary 

actuator,

and is made with the display and operating unit AZL... and the addressing button on the
actuator, which is located under the housing cover (refer to Basic Documentation
P7550).
The correct assignment of actuator functions can be checked with the help of flashing
LEDs.

For the maximum permissible cable length, refer to the Basic Documentation.
Cabling must be strictly serial (

no branching permitted!

).

Commissioning notes

·

 

Commissioning work must be carried out by qualified staff

IP 54

Mounting example

Housing cover

ESD

Addressing

Cable length
Topology

Summary of Contents for SQM45 Series

Page 1: ...60 120 s 1 Depending on the basic unit LMV Versions Choice of drive shafts refer to Type summary The SQM45 SQM48 and this Data Sheet are intended for use by OEMs which integrate the actuators in their products Use The actuators of the SQM45 SQM48 range are used to drive gas dampers air dampers oil control valves and other ancillary equipment When used in connection with burner controls or electron...

Page 2: ... avoid inadmissible loads on bearings caused by rigid hubs it is recommended to use compensating clutches with no mechanical play e g metal bellows clutches Only the specified cable may be used refer to Basic Documentation P7550 The ca ble s shielding must be connected to the printed circuit board using the tab provided Ensure that the actuator s housing is connected to functional earth FE of the ...

Page 3: ...reduced when the actuator s power supply is switched off The housing cover may only be removed for short periods of time for wiring or when making the addressing It must be made certain that dust or dirt will not get inside the actuator while such work is carried out The actuator contains a printed circuit board with ESD sensitive components The top side of the board carries a cover which affords ...

Page 4: ...ved Mechanical design The housing is made of die cast aluminium The cover is made of impact proof and heat resistant plastic Color of cover Black Stepper motor In connection with the basic unit e g LMV51 Via the display and operating unit AZL5X refer to Basic Documentation P7550 RAST3 5 terminals supplied together with the AGG5 720 AGG5 721 SQM45 Spur gears made of plastic with small backlash and ...

Page 5: ...e the torque is about 3 Under nominal conditions Under extreme conditions below 15 C ambient temperature the available torque is about 15 lower 15 lower Ordering When ordering please give type references of actuator and accessories according to Type summary In addition to the actuator the following item is to be ordered separately and is also supplied as a separate item Shielded cable Special term...

Page 6: ...tion of rotation can be selected on the basic unit Torques and holding torques refer to Type summary Reproducibility typically in the show room condition 0 2 when used with the basic unit LMV51 Running times refer to Type summary can be selected on the basic unit Load changes with continuous heavy loads SQM45 SQM48 497 SQM48 697 typically 500 000 typically 300 000 Weight SQM45 SQM48 approx 1 kg ap...

Page 7: ...the Basic Documentation of the LMV The running times of the associated controlling elements are varied by the basic unit depending on the burner s control phase e g startup phase short running time opera tion long running time Terminating resistor At the end of the serial bus cabling a terminating resistor must be fitted For that purpose a jumper must be set to BUS TERMINATION on the last actuator...

Page 8: ...8 ø16 ø10 ø14 5 7 D shaft Prepared for self tapping screws M5 10 mm deep to DIN 7500 8 5 0 0 05 1 ø18 7814m01e 1102 90 76 50 25 5 2 x Pg11 22 6 17 25 12 ø16 SQM45 SQM48 36 39 2 28 33 137 122 87 25 41 116 2 6 15 47 Groove for Woodruff key 3x3 7 to DIN 6888 Groove for parallel key A5x3x28 to DIN 6885 T3 1 5 SQM45 SQM48 ã 2002 Siemens Building Technologies Subject to change ...

Reviews: