background image

7

Siemens

A6V12681516_enUS_a

Smart Infrastructure

10/12/2022

3.  Connect or disconnect wire terminals (terminal block is removable)

4.  Install the cover

5.  Screw in the cover screw

Maintenance

The actuators require no maintenance.

 WARNING

Operating voltage must be switched off during any maintenance!

NOTICE

When carrying out service work on the plant, note the following:

  Switch off operating voltage.

  If necessary, disconnect electrical connections from the terminals.

  The actuator must be commissioned only with a correctly mounted valve in place!

Repair

The actuators cannot be repaired; the complete unit must be replaced.

Disposal

The device is considered an electronic
device for disposal and may not be disposed
of as domestic waste.

  Dispose of the device through channels

provided for this purpose.

  Comply with all local and currently

applicable laws and regulations.

Warranty

Technical data on specific applications are valid only together with Siemens products listed
under "Equipment combinations". Siemens rejects any and all warranties in the event that
third-party products are used.

Summary of Contents for SSB161.05U

Page 1: ...4 V positioning signal DC 0 10 V Self calibrating to the valve stroke Direct mounting with coupling nut no tools required Manually override Position and actuator motion indication LED Positioning force 45 lbf 200 N Parallel operation of multiple actuators possible A6V12681516_enUS_a Smart Infrastructure 10 12 2022 ...

Page 2: ...tended no actuator is mounted DC 0 10 V control signal The valve opens closes in proportion to the control signal at Y At DC 0 V the actuator stem is retracted the normally closed valve is fully closed and the normally open valve is fully open When no power is supplied the actuator maintains its current position Y Control signal Y V H Percentage of calibrated valve stroke LED indication Status LED...

Page 3: ...tory or ordered separately For easier valve assembly actuators ordered separately have the actuator stem fully retracted Equipment combinations Valves Combinable valves for SSB161 05U 2 way Powermite 599 MZ Series Action Nominal Line Size Flow Rate Connection Inch mm Cv Kvs FxF FxUM AFxUM Normally Closed 0 5 15 0 4 0 34 599 01100 599 01101 0 5 15 0 63 0 54 599 01102 599 01103 0 5 15 1 0 0 85 599 0...

Page 4: ... documentation Topic Title Document ID Installation Mounting instruction A6V13122037 Standards and directives CE declarations A5W00254962A RCM conformity A5W00254983A Environmental compatibility Environmental declarations A5W00242127A Related documents such as the environmental declarations CE declarations etc can be downloaded from the following Internet address www siemens com bt download Notes ...

Page 5: ...en the union nut manually See Mounting instructions for graphical instructions Orientation Commissioning When commissioning check both wiring and functioning of the actuator Actuator stem extends Normally open valve closes normally closed valve opens Actuator stem retracts Normally open valve opens normally closed valve closes NOTICE The actuator must be commissioned only with a correctly mounted ...

Page 6: ...low for at least three seconds The actuator ignores any control signal from the controller 3 Adjust the position of the actuator stem by rotating hexagonal wrench b illustrated below clockwise or counter clockwise The actuator stem moves down if you rotate clockwise it moves up if you rotate counter clockwise The manually set position is retained 4 To exit manual operation mode press and hold down...

Page 7: ...ns from the terminals The actuator must be commissioned only with a correctly mounted valve in place Repair The actuators cannot be repaired the complete unit must be replaced Disposal The device is considered an electronic device for disposal and may not be disposed of as domestic waste Dispose of the device through channels provided for this purpose Comply with all local and currently applicable...

Page 8: ...evices use Open Source Software OSS All Open Source Software components used in the product to include copyrights and licensing agreement are available at http siemens com bt download Firmware version OSS document Device Document ID Title 2 10 0 or above A6V13503690 Readme OSS for Modulating Room Actuator 200N 300N All ...

Page 9: ...contact Y See Technical design 2 Running speed time for 5 5 mm 5 s mm 25 27 5 s 25 Positioning force 45 lbf 200 N Stroke 0 05 to 0 25 inch 1 2 6 5 mm Permissible temperature of medium in the connected valve 34 to 248 F 1 120 Electrical connection Permissible length for signal lines 65 ft 20 m Wire cross section 18 20 AWG 0 5 0 75 mm Cable diameter 0 2 inch 5 mm Mounting Connection to valve Plastic...

Page 10: ...e that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and r...

Page 11: ...11 Siemens A6V12681516_enUS_a Smart Infrastructure 10 12 2022 Material Cover base PC ABS Weight 7 8 ounces 220 g ...

Page 12: ...ntrol signal DC 0 10 V G System potential AC DC 24 V Connection diagrams N Controller Y Actuator SP G System potential AC 24 V SN G0 System neutral Y Control signal Dimensions mm inch Revision numbers Type Valid from rev no SSB161 05U A G Y G0 Y SN AC 24 V DC 24 V 2AF 76 7 3 27 7 1 1 92 6 3 7 A6V12681511Z15 49 1 9 ...

Page 13: ......

Page 14: ... Global Headquarters Theilerstrasse 1a CH 6300 Zug 41 58 724 2424 www siemens com buildingtechnologies Siemens Switzerland Ltd 2022 Technical specifications and availability subject to change without notice Document ID A6V12681516_enUS_a Edition 10 12 2022 ...