background image

Siemens Building Technologies

Fire Safety

P/N 315-048733-3

System Status Display with Control

Installation Instructions
Models SSD-C / SSD-C-INTL

INTRODUCTION

The 

 Model SSD-C/

SSD-C-INTL is an optional FireFinder
module that displays the event status
of a system and has the capability to
control the system remotely from the
PMI. It has four 40 character alphanu-
meric LCD character lines, backlit upon
status change or display toggling. This
module is supervised by the main
panel and also has LEDs and an
optional sounder to indicate the status of the system. The SSD-C has the capability to
store up to 1500 event messages and has pushbuttons to scroll through these events.
Its display is independent from the display on the PMI. During the SSD-C/SSD-C-INTL
initial power up, the SSD-C/SSD-C-INTL is configured in Display-only mode.

The following items are supplied with the SSD-C/SSD-C-INTL:

•

SSD mounting plate (P/N 300-034289) with the SSD-TB interface board
(P/N 515-034170)

•

8-pin wiring interface cable (P/N 555-134347)

•

SSD-C housing (P/N 195-134170) with an SSD-C-main board (P/N 557-034170)

•

Overlay—The SSC-C has one overlay, the SSD-C-INTL has three overlays.
-

SSD-C overlay (P/N 200-134294 in English)

-

SSD-C-INTL overlays (P/N 200-134751 in French, P/N 200-134752 in
Spanish, P/N 200-134753 in Portuguese)

•

4 screws to mount the housing to the mounting bracket (P/N 545-634442)

The SSD-C-INTL is used in applications where French, Spanish or Portuguese is the
primary language. It is identical to the SSD-C in all other ways, and will be referred to
in the remainder of this document as SSD-C.

OPERATION

The SSD-C has six LEDs and a sounder to indicate the status of the fire alarm panel.
The LCD indicates the state of a specific event. The SSD-C also has push buttons that
allow the user to scroll through the events list, and/or take control of the system.

The SSD-C can be configured as Display only or with System Control and can be
used in two different vectoring applications: No Vectoring and Queue Vectoring.Refer
to the Programming section on page 7 for information on configuring the system.

Figure 1

SSD-C System Status Display

AUDIBLES

SILENCED

ON

SUPERVISORY

ALARM

RESET

TROUBLE

SECURITY

ON

OFF

ACKNOWLEDGE

SILENCE

UNSILENCE

BUTTON ENABLE

Summary of Contents for SSD-C

Page 1: ... SSD C housing P N 195 134170 with an SSD C main board P N 557 034170 Overlay The SSC C has one overlay the SSD C INTL has three overlays SSD C overlay P N 200 134294 in English SSD C INTL overlays P N 200 134751 in French P N 200 134752 in Spanish P N 200 134753 in Portuguese 4 screws to mount the housing to the mounting bracket P N 545 634442 The SSD C INTL is used in applications where French S...

Page 2: ...s present in the system then the SSD C will have full system control However if for the same SSD C there are alarms and troubles in the system then pressing a control push button Acknowledge Silence Unsilence or Reset on the SSD C will have no effect on the system The corresponding LED of the queue type not vectored will activate momentarily to indicate to the user that an event of a different que...

Page 3: ...hat all NACs in the system are in supervisory mode The Sounder operates as follows SOUNDER Normally OFF Indicates that the system is in supervi sory mode or all events in the system have been acknowledged or that a push button has been pressed ON STEADY Indicates that at least one unacknowl edged alarm is present in the system ON PULSING Indicates that at least one unacknowl edged non alarm superv...

Page 4: ...STATES CANADA Figure 2 Event Priority United States and Canada KEYSWITCH The keyswitch must be in the ENABLE position to activate the control pushbutton In the ENABLE position the key is vertically in the keyswitch in the DISABLE position the key can be removed from the keyswitch ACKNOWLEDGE During Supervisory Mode Activates LCD backlight for 10 minutes When Event Is Displayed Acknowledges the una...

Page 5: ...nd system ID Line 3 Custom message and system ID Line 4 Blank Active Event Mode Line 1 Event Status module device address date and time of the event Line 2 Custom message for the module device acknowledged non acknowledged Line 3 Event category or trouble type sequence number of the event Line 4 Total number of Alarms Supervisory Security andTrouble events in the system or vectored to the SSD C ma...

Page 6: ...unication wire by setting SW1 and SW2 to the ON position This allows the NIC C to properly supervise the communication wires S2 S3 S4 Network Address Switches Set the three digit HNET network address for the SSD C using the three ten position rotary switches located on the board See Figure 4 Each of these addresses must be the same as the addresses assigned in the Zeus ProgrammingTool The range of...

Page 7: ... selected alarm events are displayed on the SSD other wise alarm events are filtered Display Supervisory Events If selected supervisory events are displayed on the SSD otherwise supervisory events are filtered Display Security Events If selected security events are displayed on the SSD otherwise security events are filtered DisplayTroubles If selected trouble events are displayed on the SSD otherw...

Page 8: ...SD TB PAIR A EARTH GROUND CABLE TO SSD MAIN PAIR B A A B B P1 PSC 12 1 2 TB3 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 DO NOT USE DO NOT USE DO NOT USE DO NOT USE ONE SLOT OF CC 5 NIC C E TB1 TB2 Figure 6 WiringThe SSD C INSTALLATION The SSD C mounts directly onto a user supplied double gang or 4 inch switchbox Refer to Figure 7 DOUBLE GANG BOX 3 1 2 INCHES DEEP A 4 INCH SQUAR...

Page 9: ...he four corners of the SSD C Assembly Secure with the screws provided Insert the 3 bottom tabs on the appropriate overlay with the 3 corresponding slots in the bottom of the SSD C Assembly Slightly bend the overlay to align and insert the 3 top tabs into the 3 corresponding slots in the top of the SSD C Assembly Discard the remaining overlays if applicable ELECTRICAL RATINGS l a c i p y T x a M C ...

Page 10: ...Siemens Building Technologies Inc 8 Fernwood Road Florham Park New Jersey 07932 Siemens Building Technologies Ltd 2 Kenview Boulevard Brampton Ontario L6T 5E4 CN P N 315 048733 3 ...

Reviews:

Related manuals for SSD-C