4.4.3 Installing a License Card
Should a License card need to be installed / replaced the following procedure should be
followed:
1. Power down the Stratos Outstation.
2. Unplug connectors and slide the unit free of any rack so that the bottom edge of the
CPU board can be accessed.
3. Turn the circular metal locking ring with a finger to unlock the holder.
4. Lift the bottom edge of the card holder.
5. Insert the card in to the holder as shown – contact side towards board and chamfered
edge towards bottom of board.
6. Lower the holder and return the locking ring to the locked position.
For License installation see the User Interface Handbook 667/HU/46000/000.
4.4.4 Replacing the CPU card
Should the CPU card need to be replaced, see section 7.3.1 for details.
4.5
USB to 25 Way D Type Adaptor
A USB to 25W D type handset adaptor is available (667/1/47180/000), which allow
connection from legacy 25 way handset terminals to the Outstation command line
interface via the 2 USB host connections on the front of the CPU board. The cable comes
with two USB connectors; these must be both connected to provide power and
communications to the legacy handset device. The supported handset baud rates are
19200, 9600 and 1200 (all 7 data, even parity, auto baud). To reset the auto baud rate
detection, the USB connectors need to be disconnected and reconnected.