4.8.4 Changing
Fuses
See section 7.3.5 for fuse change procedure.
4.8.5 I/O Board Rotary Address Switch
This screwdriver-adjustable switch is located on the I/O board(s) as shown in Figure 12
and is set up for the board address (before the Stratos Outstation is powered up) in
accordance with the appropriate Works Specification. The valid address range is 1
through 15 (where A to F denote 10 to 15 respectively). Address 0 is the default address
switch position for spare boards.
The address range is shared with other GSPI peripheral boards and must be
unique. The Stratos Outstation PSU board is fixed at address 15 (so this
address must not be used).
4.8.6 Replacing the I/O Board
Should an I/O board need to be replaced, see section 7.3.1 for details.
4.8.7 I/O Board Kits & Assembly
The Stratos outstation supports a number I/O board options as listed below:
Description
Part Number
48-16 I/O Board Kit with cable
I/O card, RJ45 cable, BUS/MOVA Cables (x2), Spacers & Fixings
667/1/50076/000
48-16 I/O Board Kit without cable
I/O card, RJ45 cable, Spacers & Fixings
667/1/50076/002
I/O PCB Kit TC12 Adaptor
I/O card, RJ45 Cable, TC12 card & IDC interlinking cables, Spacers
& Fixings
667/1/50076/001
I/O boards are mounted using the provided spacers adjacent to the CPU board. The GSPI
RJ45 cable must be connected from the CPU board to the I/O board 'IN' connector. Any
subsequent I/O boards are mounted on the stack in the same manner and the GSPI RJ45
cable then runs from the previous I/O board 'OUT' connector to the next I/O board 'IN'
connector. The I/O cable assemblies shown in Figure 15 should be tidily cable tied to the
surrounding metalwork to reduce the strain on the connectors.