The information below shows the wiring for the lamp supply monitor input connector:
Pin
Function
1
230V Mains Live supply (LV) or -48V (ELV)
Pink Wire
2
Return (Neutral for LV, 0V for ELV)
Yellow Wire
5.10 Powering
Before powering the unit for the first time, ensure that the mains supply is correctly
protected and wired. Switch the unit on and check that the appropriate LEDs illuminate on
the PSU and CPU boards.
If the Stratos Outstation is equipped with an internal backup battery, ensure that it is
enabled by setting the front panel ‘BATTERY’ switch to the ‘ON’ position.
5.11 Installing Additional Licenses
The Stratos Outstation comes with a UTMC OTU license as standard. If additional
licenses are required they can be installed by following the procedure described in section
11 of the ST950 and Stratos Outstation User Interface Handbook 667/HU/46000/000 for
the web interface.
5.12 Configuration
To configure the UTMC OTU I/O Mapping, import the “CSV” file for the junction, modify as
necessary and save. The process is detailed in the UTMC OTU Handbook
667/HB/46000/003.
When both MOVA and UTMC OTU are configured on the Stratos Outstation, they share
the same force and reply bits on the interface to the controller, with the addition of MOVA-
specific I/O (for detectors, take-over and controller-ready). MOVA can also be configured
without UTC, using the MOVA-Only setup facility on the I/O mapping screen. If UTC is to
be added at some later date, then it is better, if possible, to configure the site for both UTC