4.8.1 I/O
LEDs
The three LEDs on the front of the I/O Board as shown below (viewed from the front).
LED
State
Description
SYSTEM / RUN
(Green)
Slow Flash
Normal Operation.
Medium
Flash
Configuration or Firmware Download in progress.
Double Pulse Low power mode (Future Feature)
COMMS
(Green)
On
Normal operation, GSPI messages being received
regularly.
Off
No relevant GSPI messages received in the last
second (implies loss of communications), or low
power mode.
FAULT
(Red)
Off
Normal operation.
On
Fault detected see fault section for details of possible
faults.
Double Pulse Firmware is in Error and low power mode.
Table 18 – PSU & I/O Board LED States
4.8.2 I/O
Faults
Presence of the following I/O board faults will cause the fault LED to be on. When the fault
LED is illuminated the fault table webpage can be accessed to determine which of the
following faults is present.
Fault
Possible cause/Remedy
Hardware error
Could be caused by one of the following
1. I/O fuse (F1) failure
- replace the fuse (section 7.3.5)
2. PSU board hardware failure
- replace the PSU board
Supply voltage low (environment error)
The PSU board supply voltage has dropped
below 8V.