9 Heating circuit control
05.02.2007
Forwarding the resulting room operating mode from the Qx relay outputs of the
RMH760B to a Synco™200 controller:
G
G0
A
C
24
V
G
G0
M D1
N2
31
21
A
0
5
G
G0
N1
Qx3
Qx4
Qx3
Qx4
M D2
N1 RMH760B
N2 Synco™200
RLU2…
Main menu > Commissioning > Extra configuration > Heating circuit 1
(or
2
or
3
)
> Outputs
Operating line
Adjustable values / display / remarks
Operating mode relay 1
--- / N.Q1…, etc. (only free relays) /
assignment of operating mode relays
Operating mode relay 2
--- / N.Q1…, etc. (only free relays) /
assignment of operating mode relays
On the “Settings” menu, the operating mode relay to be energized can be defined for
each room operating mode.
Main menu > Settings > Heating circuit 1
(or
2
or
3
)
> Space heating
Operating line
Range
Factory setting
Comfort relay control
--- / R1 / R2 / R1+R2
---
Precomfort relay control
--- / R1 / R2 / R1+R2
---
Economy relay control
--- / R1 / R2 / R1+R2
R2
Protection relay control
--- / R1 / R2 / R1+R2
R1+R2
The factory setting has been chosen such that the digital outputs can be connected
directly to the digital inputs of the Synco™200 controller.
Since the Synco™200 controllers do not use the Precomfort mode, an automatic
change from Precomfort to Comfort mode will be made. This setting can be changed to
suit individual needs.
The adjustable values previously listed under "Settings" have the following meaning:
Value set
State of relay R1
State of relay R2
---
Normal position
Normal position
R1
Operating position
Normal position
R2
Normal position
Operating position
R1+R2 Operating
position
Operating position
The
Outputs
menu shows the state of the operating mode relays:
Main menu > Heating circuit 1
(or
2
or
3
)
> Outputs
Operating line
Current state
Operating mode relay 1
Off or On
Operating mode relay 2
Off or On
Application example
Configuration of both
operating mode relays
Settings
Note on factory setting
Meaning of
adjustable values
Display values