130/238
Building Technologies
Modular Heating Controller RMH760B
CE1P3133en
HVAC Products
9 Heating circuit control
05.02.2007
•
If the Comfort heating limit is set to “----“ (none), a heating limit will only exist in
Economy mode and Protection mode . There will be no change to summer op-
eration
•
If the Economy heating limit is set to “----“ (none), the Comfort heating limit will be
active in Economy mode
and Protection mode
•
If
all 3
temperatures lie 1 °C
below
the Comfort heating limit, heat will be delivered
in Comfort mode and Precomfort mode
•
If
one of the 3
temperatures lies
above
the Comfort heating limit, the delivery of
heat will be locked
•
If
all 3
temperatures lie 1 °C
below
the Economy heating limit, the delivery of heat
will be released in Economy mode and Protection mode
•
If
one of the 3
temperatures lies
above
the Economy heating limit, the delivery of
heat will be locked
HDCmf
HDEco
TOact
TOStrDmp
TOeff
31
31D
30
Comfort
heating limit
Eco
heating limit
Whether the heating limit function shall be active in operating mode “Continuously
Comfort “ can be selected on the “Space heating“ menu.
This setting is always active, independent of whether the operating mode was switched
to “Continuously Comfort
“ or through the room operating mode contact.
Ex-
empted from this is the room control combination with an RMU7… ventilation controller;
here, the heating limit is always active.
For operation in combination with the ventilation controller, summer / winter operation
changeover is used as an overriding function.
When the attenuated outside temperature exceeds the Comfort heating limit, a change
to summer operation will take place; this also applies to operating mode “Continuously
Comfort “.
9.6
Mixing valve control
9.6.1 Control
The flow temperature setpoint determined by weather-compensated heating circuit
control generates the effectively active setpoint for mixing valve control while giving
consideration to load control.
Mixing valve control can be effected with a 3-position or DC 0…10 V actuator. The type
of actuator is to be selected via “Extra configuration“.
The following mixing valve settings apply to both the 3-position and the DC 0…10 V
actuator:
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Heating circuit 1
(or
2
or
3
)
> Mixing circuit controller
Comfort heating limit
Economy heating limit
Heating limit when Com-
fort is preselected
Summer / winter operation
(information for ventilation)
Setpoint
3-position actuator /
DC 0…10 V actuator