141/238
Building Technologies
Modular Heating Controller RMH760B
CE1P3133en
HVAC Products
9 Heating circuit control
05.02.2007
The room temperature transmitted via bus is received by the heating circuit, provided
the room zones (geographical zone (apartm.)) of the transmitter accord with those of
the receiver.
The following variants are available:
Variant Effect
Diagram
1 room sensor directly
connected
The heating circuit operates
with its own room temperature.
When communication is
activated, the room tempera-
ture signal will be delivered
throughout the heating circuit’s
geographical zone
T
Synco
2 room sensors directly
connected
The heating circuit operates
with the average value of the 2
sensors.
When communication is
activated, the average value
will be delivered throughout
the heating circuit’s geographi-
cal zone as the room tempera-
ture
Synco
T
T
1 room sensor (or
1 QAW740 room unit)
When communication is acti-
vated, the heating circuit re-
ceives the room temperature
signal of the same geographical
zone.
The heating circuit operates with
the room temperature received
T
Synco
2 room sensors or
1 Konnex room sensor
and 1 QAW740 room
unit *
When communication is
activated, the heating circuit
receives the room temperature
signals of the same geo-
graphical zone.
The heating circuit operates
with the average value of the 2
temperature signals received
T
T
Synco
1 directly connected
room sensor and
1 Konnex room sensor
(or 1 QAW740 room
unit)
When communication is
activated, the heating circuit
receives the room temperature
signal of the same geographi-
cal zone.
The heating circuit operates
with the average value of the 2
temperatures
31
4
0Z
11
T
T
Synco
* 2 QAW740 room units are not permitted! Operation in the room can only take place on one device
When using the room control combination with ventilation, special attention must be
paid to the sensor's location on the ventilation side.
Mounting the sensor for the room temperature in the extract air in combination with a
heating circuit is
not
permitted!
The sensor for room temperature control of the ventilation system must be located in
the room. If this is not observed, the heating circuit will work with the wrong tempera-
ture when the ventilation plant is shut down.
Receiving
Important