10 DHW heating
05.02.2007
Priority Size
Explanation
DHW operating mode
contact
Using the DHW operating mode contact, a fixed
operating mode can be preselected. This operating
mode overrides DHW operation selector in the
controller
DHW operation selec-
tor
Using the DHW operation selector, it is possible to
switch from operating mode Auto to a continuous
operating mode with the respective setpoint.
In operating mode Auto , the setpoint is deter-
mined by the calendar and the time switch
Special day contact
The current 24-hour program will be overridden by
the special day contact. The associated special day
program is to be set on the DHW time switch
Holiday contact
The current 24-hour program can be overridden by
the holiday contact with a fixed setpoint
Calendar
Holidays/special days
If a special day is active, the associated 24-hour
program of the DHW time switch will be activated.
Holidays, if entered, will be overridden.
If holiday mode is active, a preselected fixed set-
point can be maintained.
When using holiday operating mode Auto , DHW
heating during the holiday period will not be af-
fected
Time switch
In the time switch, the associated 24-hour program
will be activated in accordance with the current
weekday
The control priorities with DHW plant type DHW 6 are analogous to those with
DHW 0…DHW 5. Exceptions:
•
Forced charging
•
Electric immersion heater
10.3.5 DHW
setpoints
The setpoints for the operating modes (Normal / Reduced / Protection) can be prese-
lected by the plant user via operation. The setting values limit each other.
In addition, on the service level, the setpoints for the legionella program can be set. The
normal setpoint limits the setting range downward.
Main menu > DHW > Setpoints…
Operating line
Range
Factory setting
Legionella setpoint
55…140 °C
70 °C
Normal setpoint
40…70 °C
55 °C
Reduced setpoint
5…55 °C
40 °C
Frost protection setpoint
5…40 °C
5 °C
The setpoints preselected for storage tank charging or direct DHW consumption must
be matched to the setpoints of (optional) consumer control; in other words, the settings
selected here should at any point in time lie above the setpoints of consumer control. It
may be necessary to give consideration to the different time programs.
The setpoints for consumer control are described in subsection 10.11.6 “Consumer
control”.
Plant type DHW 6 (direct
DHW heating)
Setpoints (setting)
Note on consumer control
Consumer setpoints