169/238
Building Technologies
Modular Heating Controller RMH760B
CE1P3133en
HVAC Products
10 DHW heating
05.02.2007
Main menu > Commissioning > Settings > …
or
Main menu > Settings > DHW > Controller primary circuit
Operating line
Range
Factory setting
Actuator running time
1…600 s
150 s
P-band Xp
1…100 K
50 K
Integral action time Tn
0…600 s
60 s
10.7.1 Primary temperature setpoint
To be able to bring the DHW storage tank to the required setpoint or, in the case of
direct DHW heating, to the required continuous flow temperature, heat generation and
transmission and, sometimes, primary control, require a setpoint increase.
The following setpoint increase can be set on the service level depending on the se-
lected plant type.
Main menu > Settings > DHW > Controller primary circuit
Operating line
Range
Factory setting
Setp increase DHW charging
0…50 K
10 K
Setp increase mixing valve
0…50 K
10 K
Setp increase heat exchanger
0…50 K
10 K
Setpoint increase storage tank
0…50 K
2 K
The setpoint increase for DHW charging must be set with plant types using a coiled
type storage tank (DHW 1 and DHW 2).
The setpoint increase for the mixing valve is to be set with plant types using primary
mixing valves (DHW 2 and DHW 4).
The setpoint increase for the heat exchanger is to be set with plant types using a
stratification storage tank (DHW 3, DHW 4, and DHW 5), or with direct DHW heating
(DHW 6).
The setpoint increase for the storage tank is to be set with plant types using a stratifica-
tion storage tank and primary control (DHW 3 and DHW 4). This increase acts on the
setpoint of primary control, but not on the request to heat generation.
The setpoint of primary control is thus generated from the required storage tank tem-
perature setpoint plus a plant type-dependent setpoint increase.
If, with plant type DHW 4, a primary flow sensor is configured, control will be effected
according to that sensor. In that case, the heat exchanger’s setpoint increase must also
be considered for the control setpoint.
The following table shows the generation of the control setpoint:
Control via the …
Plant type
Primary flow temperature
Secondary flow temperature
DHW 2
Storage tank temperature setpoint
+
setpoint increase DHW charging
DHW 3
Storage tank temperature set-
point
+
setpoint increase storage
tank
DHW 4
Storage tank temperature setpoint
+ setpoint increase
Heat exchanger setp increase*
Storage tank temperature set-
point
+
setpoint increase storage
tank
DHW 6
DHW temperature setpoint
* Optional sensor:
The primary flow temperature setpoint will automatically be lowered when the secondary flow temperature
exceeds the secondary flow temperature setpoint by more than 1 K
Settings
Setpoint increase DHW
charging
Setpoint increase
mixing valve
Setpoint increase heat
exchanger
Setpoint increase
storage tank
Control setpoint
Primary flow sensor