Modular Heating Controller RMH760B
CE1P3133en
HVAC Products
3 Commissioning
05.02.2007
3 Commissioning
Preparations for using and commissioning the Synco™ 700 controllers must be made
by qualified staff who have been appropriately trained by SBT HVAC Products.
3.1
Entering the commissioning mode
During commissioning, both control and the plant’s safety functions remain deactivated!
The relays are deenergized, which means that their normally open contacts are open.
When supplying power to the controller for the first time, the
Language
menu appears.
Here, the language used for commissioning and operating the plant can be selected.
After the language has been selected and confirmed with the OK knob, the time of day,
date and year can be set in the same way. Then, the
Commissioning
menu will appear.
The access level is automatically set to
Password level
.
The
Plant type
menu offers a number of plant types for selection.
When the controller is commissioned for the first time, follow Installation Instructions
G3133; they are enclosed with the controller.
3.2 Basic
configuration
A plant is always configured on the password levels and (district heat parame-
ters).
Main menu > Commissioning > Basic configuration
Operating line
Adjustable values / display / remarks
Plant type
Basic type H / H0-1…H6-7
Position 1
--- / RMZ782 / RMZ783 / RMZ787 / RMZ789
Position 2
--- / RMZ782 / RMZ783 / RMZ787 / RMZ789
Position 3
--- / RMZ782 / RMZ783 / RMZ787 / RMZ789
Position 4
--- / RMZ782 / RMZ783 / RMZ787 / RMZ789
On operating line
Plant type
, the plant type will be entered or displayed.
On operating lines
Position 1
through
Position 4
, it is selected or displayed which of the
extension modules is required. If an extension module is provided for use with the
selected plant type, it is already preconfigured.
Display of
“---“ means that no module has been configured.
3.2.1
Selecting the plant type
The first setting to be made is always the plant type because when selecting the type of
plant, the majority of settings are reset to their default values.
Following will not be reset:
•
Texts
•
Business card
•
Device name
•
Terminal types
•
Time switch
•
Holiday program
The RMH760B contains 41 plant types. If required, every type of plant can subse-
quently be changed or complemented via “Extra configuration”.
Plant type
Position
Setting
Plant types