3 Commissioning
05.02.2007
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Inputs > …X…
Operating line
Range
Factory setting
Type reference
Ni 1000 / 2 × Ni 1000 /
T1 / Pt 1000 /
DC 0…10 V / NTC 575*
Ni 1000
* For outside temperature only
Type of signal
Type of sensing element /
signal
Measuring range
Passive temperature signals LG-Ni 1000
−
50…
+
250 °C
Passive temperature signals 2 x LG-Ni 1000 / T1
−
50…
+
150 °C
Passive temperature signals Pt1000
−
50…+400 °C
Active signals
DC 0…10 V
Selectable. To be
entered are a low and
a high limit
Passive temperature signals NTC575*
−
50…+500 °C
* For outside temperature only
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Inputs > …X…
Operating line
Range
Factory setting
Value low
Depending on the
selected type
Depending on
the type
Value high
Depending on the
selected type
Depending on
the type
Flow temperature with an active signal of DC 0…10 V = 0…100 °C:
Lower limit value: 0 °C
Upper limit value: 100 °C
With passive temperature sensors, the measured value can be readjusted by
−
3.0…
+
3.0 K to compensate for line resistance. It is thus possible to make onsite
calibrations with a reference instrument.
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Inputs > …X…
Operating line
Range
Factory setting
Correction
−
3.0…3.0 K
0.0 K
When the
Commissioning
menu is quit, a check is made to see which sensors are
connected. If, later, one of the sensors connected at this point in time is missing, or if
there is a short-circuit, a fault status message
[…] sensor error
will be delivered.
If there is an error on the measuring line, the operator unit will display the measured
value as follows:
•
Open-circuit = ----
•
Short-circuit =
oooo
Potential-free contacts for control functions can be connected to the digital inputs.
Main menu > Commissioning > Extra configuration > Miscellaneous > Input identifier
Operating line
Adjustable values / display / remarks
Display input 1
Digital
Setting
Measuring range
Setting
Example
Measured value correc-
tion
Setting
Fault handling
Digital inputs
Configuration