153/238
Building Technologies
Modular Heating Controller RMH760B
CE1P3133en
HVAC Products
10 DHW heating
05.02.2007
10.3.3 Plant
operation
Plant operation indicates whether DHW heating is switched on and what its state is.
Main menu > DHW > Plant operation
Operating line
Range
Factory setting
Preselection
Auto / Off*
Auto
State
Off /
DHW ready /
Charging active /
Electric
Cause
Plant operation sel /
DHW user request /
Legionella function /
Overtemp protec-
tion/overrun /
Frost protection storage
tank /
Frost protection for the
flow /
Summer operation /
* The frost protection functions are ensured (according to control priority
d
, refer to subsection 10.3.4)
For service purposes, DHW heating can be switched off. The primary valve will fully
close, the pumps start their overrun and will then be deactivated.
On completion of servicing, the plant operation selector must be set back to “Auto“.
The current state of DHW heating is displayed.
It is indicated why the current state is active.
10.3.4 Control
priorities
in DHW heating mode
The following diagram shows the priorities of the different choices of intervention via
digital inputs and via operation on the controller.
Lower numbers indicate higher priorities.
Plant operation
Preselection for the plant
operation selector
State
Cause
Plant types
DHW 0…DHW 5
⇒