12 Function block miscellaneous
05.02.2007
12
Function block miscellaneous
12.1 Overview of function block
a
x x x
x
a
Q
a
Di
sp
la
y 1
Di
sp
la
y 2
Di
sp
la
y 3
Di
sp
la
y 4
Wi
nd
So
la
r
Ou
ts
id
e
Miscellaneous
12.2 Configuration
Function block “Miscellaneous“ is always available. To activate the function block, no
special basic configuration is required.
The common functions required for the plants can be activated via “Extra configura-
tion”.
Main menu > Commissioning > Extra configuration > Miscellaneous > Inputs
Operating line
Adjustable values / display / remarks
Outside temperature sensor
Solar radiation
Wind speed
Display input 1
Display input 2
Display input 3
Display input 4
Main menu > Commissioning > Extra configuration > Miscellaneous > Outputs
Operating line
Adjustable values / display / remarks
Outside temperature relay
Main menu > Commissioning > Extra configuration > Miscellaneous
Operating line
Range
Factory setting
Business card
Yes / No
Yes
Activation of the business card is described in subsection 4.5.4 “Electronic business
card”.
12.3 Outside
sensor
A total of 3 outside sensors can be connected to the RMH760B:
•
The outside sensor at function block “Miscellaneous“ can be used as follows:
−
As a reference variable for flow temperature control and for other functions in
connection with heating circuit 1
Extra configuration
Inputs
Outputs
Functions
Business card