48/238
Building Technologies
Modular Heating Controller RMH760B
CE1P3133en
HVAC Products
5 General functions, fundamentals
05.02.2007
Entry Effect
Diagram
Slave
The holidays / special day program of this
heating circuit or of DHW is not active; a
holidays / special day program selected on
the slave will be ignored.
Active is some other holidays / special day
program assigned to the same holidays /
special day zone. This holidays / special day
program must be set as the master holidays /
special day program.
Master
The holidays / special day program is set as
the master. It acts on all internal and external
holidays / special day programs set as slaves
and lying in the same holidays / special day
zone.
31
40
Z09
Main menu > Commissioning > Communication > Room heating circuit 1
(or
2
or
3
)
Main menu > Commissioning > Communication > DHW
Operating line
Range
Factory setting
Holidays/special day operation
Autonomous / Slave /
Master
Autonomous
Holidays / special day zone
1…31 1
For details on the settings relating to holidays / special day communication, refer to
chapter 5.2.2 „Holidays “.
5.2.2 Holidays
Holidays are periods of time
•
during which the building is not occupied
•
whose start and duration are known in advance
Examples:
•
Works holidays in commercially used spaces and buildings
•
School holidays in school buildings
•
Public holidays
The operating mode to be used during the holiday period can be set separately for
each heating circuit and each DHW heating system. The following operating modes can
be selected for the heating circuits:
•
Economy
•
Protection
Following can be selected for DHW heating:
•
Auto
•
Normal
•
Reduced
•
Protection
For the circulating pump, following applies during the holiday period:
•
If “Protection“
has been selected as the DHW operating mode during the holiday
period, the circulating pump will be deactivated
•
In the other operating modes, the circulating pump will run according to the time
program
For the legionella function, following applies during the holiday period:
•
If “Protection“
has been selected as the DHW operating mode during the holiday
period, the legionella function will be deactivated
•
In the other operating modes, the legionella function will remain activated
Circulating pump
Legionella function