127/232
Building Technologies
Boiler sequence controller RMK770
CE1P3132en
HVAC Products
7 Boiler control
23.04.2009
7.15 Fault status messages
This section 7.15 shows the text for each fault number with which the controller is
supplied. It can be changed on the password level.
Number Text
(as
supplied)
Effect
301
[Boiler 1] boiler sensor
error
Urgent message; must be acknowledged.
No boiler stop
302
[Boiler 2] boiler sensor
error
Urgent message; must be acknowledged.
No boiler stop
303
[Boiler 3] boiler sensor
error
Urgent message; must be acknowledged.
No boiler stop
304
[Boiler 4] boiler sensor
error
Urgent message; must be acknowledged.
No boiler stop
305
[Boiler 5] boiler sensor
error
Urgent message; must be acknowledged.
No boiler stop
306
[Boiler 6] boiler sensor
error
Urgent message; must be acknowledged.
No boiler stop
If the boiler temperature sensor is faulty, the burner is shut down.
Number Text
(as
supplied)
Effect
311
[Boiler 1] return sensor
error
Nonurgent message; must be acknowl-
edged. No boiler stop
312
[Boiler 2] return sensor
error
Nonurgent message; must be acknowl-
edged. No boiler stop
313
[Boiler 3] return sensor
error
Nonurgent message; must be acknowl-
edged. No boiler stop
314
[Boiler 4] return sensor
error
Nonurgent message; must be acknowl-
edged. No boiler stop
315
[Boiler 5] return sensor
error
Nonurgent message; must be acknowl-
edged. No boiler stop
316
[Boiler 6] return sensor
error
Nonurgent message; must be acknowl-
edged. No boiler stop
In the case of plant with mixing valve for the maintained boiler return temperature, the
mixing valve is driven to the fully closed position when there is no return temperature
sensor and then deenergized to make possible manual adjustment.
Otherwise, the control behaves like a plant without return temperature sensor.
Number Text
(as
supplied)
Effect
321
[K1] flue gas temp sensor
error
Nonurgent message; must be acknowl-
edged. No boiler stop
322
[K2] flue gas temp sensor
error
Nonurgent message; must be acknowl-
edged. No boiler stop
323
[K3] Flue gas temp
sensor error
Nonurgent message; must be acknowl-
edged. No boiler stop
324
[K4] flue gas temp sensor
error
Nonurgent message; must be acknowl-
edged. No boiler stop
325
[K5] flue gas temp sensor
error
Nonurgent message; must be acknowl-
edged. No boiler stop
326
[K6] flue gas temp sensor
error
Nonurgent message; must be acknowl-
edged. No boiler stop
Note
Fault boiler temperature
sensor
Fault return temperature
sensor
Fault flue gas
temperature sensor