199/232
Building Technologies
Boiler sequence controller RMK770
CE1P3132en
HVAC Products
13 Function block “Faults“
23.04.2009
Extended faults are faults that must be acknowledged
and
reset. This is the case with a
twin pump, for example, when both pumps signal a fault. The pumps start running again
only after the fault has been acknowledged, corrected and reset.
31
3
1B
12
LED lit
LED flashes
LED off
No fault,
acknowledged,
reset
LED flashes
LED lit
Aggregate or plant stopped
Fault
going
Faulty,
acknowledged
Faulty, not
acknowledged
Acknowledge
fault
Fault
going
Fault
coming
No fault,
acknowledged
No fault, not
acknowledged
Fault
coming
Acknowledge
fault
13.7 Predefined fault inputs
With function blocks “Boiler sequence manager“, “Boiler 1…6” and the pump blocks,
predefined fault inputs are available.
For a description of these fault inputs, refer to the relevant function blocks. The parame-
ters of these fault inputs are also set on the respective function blocks.
13.8 Fault
inputs
13.8.1 Universal fault inputs
The RMK770 provides 4 universal fault inputs. These can be activated in the extra
configuration.
Analog or digital inputs can be defined as fault inputs. Inputs D1 and D2 at the RMK770
can only be used as digital fault inputs.
If the input is not assigned to an input that has already been configured, the input identifier
and thus the type of input or the unit can be freely selected.
Main menu > Commissioning > Extra configuration > Faults > Input identifiers
Operating line
Range
Factory setting
Fault input 1
°C / % / g/kg / kJ/kg /
W/m2 / m/s / bar / mbar
/ Pa / ppm / Universal
0000.0 / Universal
000.0 / Universal 0000 /
Digital
Digital
Fault input 2
Like fault input 1
Digital
Fault input 3
Like fault input 1
Digital
Fault input 4
Like fault input 1
Digital
With a digital input, it is also possible to define the normal position.
Extended faults