217/232
Building Technologies
Boiler sequence controller RMK770
CE1P3132en
HVAC Products
15 Fault tracing support
23.04.2009
Number
Name (as supplied)
For explanation, refer to section …
5532
>1 boiler with address number 3
14.6
5542
>1 boiler with address number 4
14.6
5552
>1 boiler with address number 5
14.6
5562
>1 boiler with address number 6
14.6
5591
Failure boiler sequence manager
14.6
5592
>1 boiler sequence manager
14.6
5593
Number of boilers wrong setting
6.8
5594
Invalid lead boiler
6.8
6001
>1 identical device address
14.6
7101
Fault extension module
3.3.6
7102
Fault extension module 2
3.3.6
7103
Fault extension module 3
3.3.6
9000
>1 fault input fault
13.8.1
9001
[Fault input 1] fault
13.8.1
9002
[Fault input 2] fault
13.8.1
9003
[Fault input 3] fault
13.8.1
9004
[Fault input 4] fault
13.8.1
9401
No pulse signal meter 1
11.3.8
9402
No pulse signal meter 2
11.3.8
9403
No pulse signal meter 3
11.3.8
9404
No pulse signal meter 4
11.3.8
15.2 Rectification of faults
Question Reply
E.g., fault status message
“[HC 1] error flow sensor“ ap-
pears although a sensor is
connected.
Check to see if, in addition, fault “Fault extension
module“ occurred. This fault can lead to the
display of subsequential faults.
When commissioning the plant,
the wrong language was se-
lected.
How do I find the language I
need?
1. Press the ESC button and the OK knob simul-
taneously.
2. Choose the password level and enter number
112
as the password (same as international
emergency call) and confirm by pressing the
OK knob. The language changes to English.
3. Select your language from the
Settings > Device
> Language
menu.
The device is completely
switched off, “Operation locked,
Remote operation” appears.
How do I start the device again?
Remote operation (OCI700.1) set the device to
commissioning mode, which has locked local
operation.
If the device is not corrected restarted via remote
operation, it maintains this state. Locally, the
device can only be restarted by briefly discon-
necting the power supply.
The buttons on the QAW740
room unit do not work.
The room operating mode on the controller is
overridden by a higher priority.