41/232
Building Technologies
Boiler sequence controller RMK770
CE1P3132en
HVAC Products
3 Commissioning
23.04.2009
Main menu > Commissioning > Extra configuration > Heating circuit > Outputs
Operating line
Range
Name
Mixing valve 3-pos
HCtrVlvMx
Mixing valve modulating
HCtrVlvMx
Heating circuit pump
RMK770…, RMZ7…*
HCtrPu
Heating circuit pump B
HCtrPu_B
* Here, the free outputs are available for selection
Function block “Heating circuit” can be used as a “virtual heating circuit“. It calculates a
weather-compensated flow temperature setpoint, but does not deliver any output
signals (hence, pump or mixing valve for the heating circuit is not a mandatory require-
ment!). The weather-compensated flow temperature setpoint is delivered to the main
flow and acts as weather-compensated heat demand.
The setting to be selected is “Heating circuit active“; the heating circuit entries are made
on the operator unit as usual. No output terminals are configured.
When a heating circuit pump and/or heating circuit mixing valve is/are configured, the
heating circuit is automatically activated; a “real” heating circuit is created. In that case,
setting “Heating circuit active/inactive“ is of no importance.
This setting defines whether the heating circuit is “connected” directly to the main
header or downstream from the primary controller.
Flow temperature sensor
Room temperature sensor
Return temperature sensor
Digital input for activating the “Special day“ function.
Digital input for activating the “Holidays“ function.
Heating circuit pump A (the menu item does show designation ”A”).
Heating circuit pump B, if the heating circuit pump is a twin pump
3-position or modulating mixing valve for the heating circuit
For more detailed information, refer to chapter 10 “Heating circuit control” .
3.4.5 Miscellaneous
At menu item
Miscellaneous
of the extra configuration, the following settings can be
made:
Main menu > Commissioning > Extra configuration > Miscellaneous > Inputs
Operating line
Range
Name
Outside sensor
RMK770…, RMZ7…*
Display input 1
Display input 2
Display input 3
Display input 4
* Here, the free inputs are available for selection
Virtual heating circuit
Real heating circuit
Heat req heat circuit
acting on
Flow sensor (TFlPrCtr)
Room sensor (Tr)
Return sensor (TRtPrCtr)
Special day input
Holidays input
Heating circuit pump A
(HctrPu_A)
Heating circuit pump B
(HCtrPu_B)
Mixing valve for heating
circuit (HCtrVlVMx)
Settings