70/232
Building Technologies
Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
5 General functions, fundamentals
23.04.2009
Main menu > …. > Inputs/setpoints >
Operating line
Remarks
Optg hours pump
0…99'999 h
Optg hours pump B
0…99'999 h
Main menu > …. > Inputs/setpoints >
Operating line
Range
Factory setting
Optg hours pump
0…99'999 h
0 h
Optg hours pump B
0…99'999 h
0 h
5.8.2
Pump supervision and twin pumps
Every pump (main pump, boiler pump, system pump, heating circuit pump) can be
monitored with a fault input and flow switch.
Every pump used can be a twin pump.
Q
d d
B
d
31
32Z
22
V
Q
1)
The decision whether a pump is installed as a single or twin pump is made in the extra
configuration
with the relevant function block
(boiler sequence, boiler, primary
controller, heating circuit).
Main menu > Commissioning > Extra configuration > Boiler sequence manager > Outputs
Main menu > Commissioning > Extra configuration > Boiler … > Outputs
Main menu > Commissioning > Extra configuration > Primary controller > Outputs
Main menu > Commissioning > Extra configuration > Heating circuit > Outputs
Operating line
Adjustable values / remarks
…pump Assign
terminal
…pump B
Assign terminal
When, in addition to the pump, pump B is configured, a single pump becomes a twin
pump.
For this second pump, there is also a fault input available. The flow switch is used by
both pumps.
Main menu > Commissioning > Extra configuration > Boiler sequence manager > Inputs
Main menu > Commissioning > Extra configuration > Boiler … > Inputs
Main menu > Commissioning > Extra configuration > Primary controller > Inputs
Main menu > Commissioning > Extra configuration > Heating circuit > Inputs
Operating line
Adjustable values / remarks
[…pump] overload
Assign terminal
[…pump B] overload
Assign terminal
Flow signal pump
Assign terminal
If a twin pump was configured, the relevant function block shows menu item
Twin pump
.
Display values
Setting values
Setting
Setting