122/148
Siemens Building Technologies
Commissioning instructions OZW775 V2.01
CE1C5663en
HVAC Products
Appendix
22.06.2012
Configure the IP address of the web server OZW775 on one or several public ports. A
public port is the port used from the Internet.
The local port is the port for the web server OZW775. You cannot change this port, i.e.
the web server always uses port 80.
Internet data from the web browser are routed via public ports 8080 and 80 to IP
address 192.168.1.180 of the web server with port 80.
Public port: 8080, 80 HTTP (web pages), data from Internet.
Local port: 80
Web server port number.
Public port: 50005
ACS, data from Internet.
Local port: 50005
Web server port number.
Public port: 49194
ACS Alarm, data from Internet.
Local port: 49194
Web server port number.
History File, Offline Trend
1)
Public Port: 21
FTP (File Transfer Protocol), data from Internet.
Local port: 21
Web server port number.
1)
This function is supported from ACS CD V5.10. The DSL router can already be configured.
Local IP address
192.168.1.180
IP address of the web server OZW775 (central comm. unit).
Comment
OZW775
Name to identify device.
The configured firewall services are activated automatically for "Local IP address".
Router SX763 does not need any other firewall settings.
Port Forwarding
Operate using
web browser
Operate using
ACS software
1)
Remote alarming
ton ACS Alarm
1)
ACS File Transfer
1)
Note