125/148
Siemens Building Technologies
Commissioning instructions OZW775 V2.01
CE1C5663en
HVAC Products
Appendix
22.06.2012
IP address:
192.168.1.1
Router address
Subnet mask
255.255.255.0
IP subnet mask
DHCP server:
On
Web server OZW775 does not support DHCP client
function. However, we recommend to still enable this func-
tion for PC clients and other devices on the LAN.
Lease time:
30 min
Validity
First issued IP address:
192.168.1.30
Start of IP address range for DHCP server
Last issued IP address:
192.168.1.80
End of IP address range for DHCP server
Default gateway:
192.168.1.1
The router often is a default gateway
Preferred DNS server:
(Blank) or DNS server 1
Alternate DNS server:
(Blank) or DNS server 2
Domain name:
(Blank) or domain for working group
MAC address:
(Blank) clients receive their static address
from the DHCP pool
Web server OZW775 uses a static IP address. Select an IP address outside the DHCP
range (see First/Last issued IP address) for web server OZW775, e.g. 192.168.1.180.
7.2.4 Configure web server OZW775
You need a PC/laptop with ACS V5.02 installed to configure web server OZW775. For
configuration, web server and PC/laptop are connected via USB interface or service
interface OCI700.
Settings > Communication > Ethernet
•
IP address:
192.168.1.180
•
IP subnetwork address: 255.255.255.0 (subnet mask)
•
Default gateway:
192.168.1.1
•
DNS server 1:
195.186.1.1
•
DNS server 2:
(blank)
•
UPnP localization:
---
You do not need to address DNS server 2 (used only in redundant systems).
Setting values
Note
Ethernet
Note